Loading...
Ordinance 2001-06 ORDINANCE NO. ~/- C1.p AN ORDINANCE OF THE CITY OF WYLIE, TEXAS, ADOPTING THE 1999 EDmON OF THE NATIONAL ELECTRICAL CODE, AND REPEALING WYLIE ORDINANCE NO. 94-53; PROVIDING FOR A PENALTY FOR THE VIOLATION OF THIS ORDINANCE; PROVIDING FOR REPEALING, SAVINGS AND SEVERABILITY CLAUSES; PROVIDING FOR AN EFFECTIVE DATE OF THIS ORDINANCE; AND PROVIDING FOR THE PUBLICATION OF THE CAPTION HEREOF. WHEREAS, the City Council of the City of Wylie, Texas ("City Council") has investigated and determined that it would be advantageous and beneficial to the citizens of the City of Wylie, Texas ("Wylie") to adopt the 1999 Edition of the National Electrical Code and to repeal Wylie Ordinance Nos. 94-53; and WHEREAS, the Construction Board and the building official for Wylie have reviewed the 1999 Edition of the National Electrical Code and both recommend adoption of the same by the City Council. NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF WYLIE, TEXAS: SECTION 1: Findin2s Incoroorated. The findings set forth above are incorporated into the body of this Ordinance as if fully set forth herein. SECTION 2: Adootion of the 1999 National Electrical Code. The National Electrical Code, 1999 Edition, copyrighted by the National Fire Protection Association is hereby adopted as the electrical code for Wylie. One (1) copy of the 1999 National Electrical Code are on file in the office of the City Secretary of Wylie being marked and designated as the National Electrical Code, 1997 Edition, copyrighted by the National Fire Protection Association. SECTION 3: Amendments to Article 210. A Article 210-61 of the 1999 National Electrical Code is hereby amended to read as follows: Article 210-61. Uses other than Dwelling Units. The following listed buildings shall have a minimum of one receptacle installed for every 20 linear feet measured horizontally around the interior wall at the floor level of each room, excluding storage rooms: ( a) Office buildings. (b) Mercantile buildings. ( c) Restaurants. (d) Taverns. Ordinance No. dIXJ{ - D(p Page 2 (e) Bank buildings. (t) Mechanical garages. (g) Studios SECTION 4: Amendments to Article 220. A Article 220-22 of the 1999 National Electrical Code is hereby amended to read as follows: Section 220-22. Feeder or Service Neutral Load. The feeder or service neutral conductor shall be sized no smaller than the size of the ungrounded conductors. Exception: The feeder or service neutral conductor may be downsized a maximum of two wire sizes provided that the electrical calculations are submitted by an electrical engineer and approved by the building official. SECTION 5: Amendments to Article 230. A Article 230-2(a) of the 1999 National Electrical Code is hereby amended to read as follows: Section 230-2 (a) Special Conditions. Additional services shall be permitted to supply (1) Fire pumps (2) Emergency systems (3) Legally required standby systems (4) Optional standby systems (5) Parallel power production systems (6) In supplying electrical service to multifamily dwellings, two or more laterals or overhead service drops shall be permitted to a building when both of the following conditions are met: a. The building has six or more individual gang meters and all meters are grouped t the same location. b. Each lateral or overhead service drop originates from the same point of service. c. B. Article 230-71(a) of the 1999 National Electrical Code is hereby amended to read as follows: Section 230-71 (a) General. The service disconnection means for each service permitted by Section 230-2, or for each set of service-entrance conductors permitted by Section 230-40, Exception Nos. 1 or 3, shall consist of not more than six switches or six circuit breakers mounted in a single enclosure, in a group of Ordinance No. ~O I - O{O Page 3 separate enclosures, or in or on a switchboard. There shall be no more than six disconnects per service grouped in anyone locations. For the purpose of this section, disconnecting means used solely for power monitoring equipment or the control circuit of the ground fault protection system, installed as part of the listed equipment, shall not be considered a service disconnecting means. Exception: Multi-occupant Buildings. Individual service disconnecting means is limited to six for each occupant. The number of individual disconnects at one locations may exceed six. SECTION 6: Amendments to Article 250. A Article 250-50 of the 1999 National Electrical Code is hereby amended to read as follows: Section 250-50. Grounding Electrode System. If available on the premises at each building or structure served, each item ( a) through (d), and any made electrodes in accordance with sections 250-52(c) and (d), shall be bonded together to form the grounding electrode system. The bonding jumper( s) shall be installed in accordance with sections 250-64(a), (b), and (e), shall be sized in accordance with Section 250-66, and shall be connected in the manner specified in Section 250-70. An unspliced grounding electrode conductor shall be permitted to be run to any convenient grounding electrode available in the grounding electrode system or to one or more grounding electrode( s) individually. It shall be sized for the largest grounding electrode conductor required among all the electrodes connected to it. The grounding electrode conductor shall be unspliced or spliced by means of irreversible compression-type connectors listed for the purpose or by the exothermic welding process. Interior metal water piping located more than 5 ft (1.52 m) from the point of entrance to the building shall not be used as a part of the grounding electrode system or as a conductor to interconnect electrodes that are part of the grounding electrode system. Exception: In industrial an commercial buildings where conditions of maintenance ans supervision ensure that only qualified persons will service the installation and the entire length of the interior metal water pipe that is being used for the coqductor is exposed. Where a metal underground water pip, as described in item (a), is present, a method of grounding as specified in (b) through (d) below shall be used. Ordinance No. grot - ()(, Page 4 FPN: See Sections 547-8 and 547-9 for special grounding and bonding requirements for agricultural buildings. Paragraphs (a) through (d) of Section 250-50 will remain as written in the 1999 National Electrical Code. B. Article 250-1 04(b) of the 1999 National Electrical Code is hereby amended to read as follows: Section 250-104(b) Metal Gas Piping. Each interior portion of a metal gas piping system upstream from the equipment shutoff valve shall be sized in accordance with Table 250-122 using the rating of the circuit that may energize the gas piping. SECTION 7: Amendments to Article 310. A Article 310-2 of the 1999 National Electrical Code is hereby amended to read as follows: Section 310-2. Conductors (a) Insulated. Conductors shall be insulated. Exception: Where covered or bare conductors are specifically permitted elsewhere in this Code. FPN: See Section 250-184 for insulation of neutral conductors of a solidly grounded high-voltage system. (b) Conductor Material. Conductors in this article shall be of copper. Aluminum or copper-clad aluminum conductors shall not be used in the City of Wylie as an electrical conductor. B. Article 310-15(b)( 6) of the 1999 National Electrical Code is hereby amended to read as follows: Section 310-15(b)(6) 1201240-Volt, 3-Wire, Single-Phase Dwelling Services and Feeders. For dwelling units, conductors, as listed in Table 310-15(b)(6) shall be permitted as 120/240-volt, 3-wire, single-phase service-entrance conductors, service lateral conductors, and feeder conductors that serve as the main power feeder to a dwelling unit and are installed in raceway or cable with or without an equipment grounding conductor. For application of this section, the main power feeder shall be the feeder( s) between the main disconnect and the lighting conductors to a dwelling unit shall not be required to be larger than their service-entrance conductors. The grounded conductor shall be permitted to be Ordinance No. tJOO L- Of., Page 5 smaller, than the ungrounded conductors, provided the requirements of Sections 215-2, 220-22, and 230-42 are met. This section shall not be used in conjunction with Section 220-30. SECTION 8: Amendments to Article 336. A Article 336-5 of the 1999 National Electrical Code is hereby amended to read as follows: Article 336-5. Uses Not Permitted. (a) Types NM, NMC, and NMS cables shall not be used in the following: (1) In any multifamily dwelling or other structure exceeding three floors above grade. F or the purpose of this article, the first floor of a building shall be that floor that has 50 percent or more of the exterior wall surface area level with or above finished grade. One additional level that is the first level and not designed for human habitation and used only for vehicle parking, storage, or similar use shall be permitted. Exception: An additional level shall be permitted in multifamily dwellings where the entire structure is protected throughout by an approved automatic sprinkler system. (2) As service-entrance cable (3) In commercial garages having hazardous (classified) locations as provided in Section 511-3 (4) In theaters and similar locations, except as provided in Article 518, Places of Assembly (5) In motion picture studios (6) In storage battery rooms (7) In hoistways (8) Embedded in poured cement, concrete, or aggregate (9) In any hazardous (classified) locations, except as permitted by Sections 501-4(b), Exception, 502-4(b), Exception, and 504-20 (10) In non-residential metal frame structures (b) Types NM and NMS. Types NM and NMS cable shall not be installed in the foll<?wing: (1) Where exposed to corrosive fumes or vapors (2) Where embedded in masonry, concrete, adobe, fill, or plaster Ordinance No. ~ Page 6 (3) In a shallow chase in masonry, concrete, or adobe and covered with plaster, adobe, or similar finish SECTION 9: Amendments to Article 336. A Article 550-13 of the 1999 National Electrical Code is hereby amended to read as follows: Article 550-13. Calculations. The following method shall be used for supply- cord mobile homes only. All others shall follow 310-15 (6) Dwelling Services and Feeders. SECTION 10: Penalty Provision. Any person, firm, corporation or business entity violating this Ordinance shall be deemed guilty of a misdemeanor, and upon conviction thereof shall be subject to a fine not to exceed the sum of FIVE HUNDRED DOLLARS ($500.00), unless the violation relates to fire safety, zoning or public health and sanitation, including dumping and refuse, in which the fine shall not exceed the sum of TWO THOUSAND AND NOIlOO DOLLARS ($2,000.00). Each continuing day's violation under this Ordinance shall constitute a separate offense. The penal provisions imposed under this Ordinance shall not preclude Wylie from filing suit to enjoin the violation. Wylie retains all legal rights and remedies available to it pursuant to local, state and federal law. SECTION 11: Savin2s/Reoealin2 Clause. All provisions of any ordinance in conflict with this Ordinance are hereby repealed to the extent they are in conflict; but such repeal shall not abate any pending prosecution for violation of the repealed ordinance, nor shall the repeal prevent a prosecution from being commenced for any violation if occurring prior to the repeal of the ordinance. Any remaining portions of said ordinances shall remain in full force and effect. SECTION 12: Severabilitv. Should any section, subsection, sentence, clause or phrase of this Ordinance be declared unconstitutional or invalid by a court of competent jurisdiction, it is expressly provided that any and all remaining portions of this Ordinance shall remain in full force and effect. Wylie hereby declares that it would have passed this Ordinance, and each section, subsection, clause or phrase thereof irrespective of the fact that anyone or more sections, subsections, sentences, clauses and phrases be declared unconstitutional or invalid. SECTION 13: Effective Date. This Ordinance shall become effective from and after its adoption and publication as required the City Charter and by law. PASSED ~ROVED by the City Council of the City of Wylie, Texas this of-L1:Vl , 2001. 16 day Ordinance No. 8COl -- D(p Page 7 C-kQ S(~H Joel Scott, Mayor Pro Tern ATTEST: r , , J \ \" I " \.... -,~' ..~,.,,--,-,; APPROVED AS TO FORM: Richard Abernathy, City Attorney DATE(S) OF PUBliCATION m a-uA / tol} '2-00 \ THE WYLIE NEWS Covering Wylie, Sachse, Murphy and the surrounding area 1]0 N. Ballard St. P.O. Box 369 Wylie, Texas 75098 972.442.5515 Fax 972.442.4318 STATE OF TEXAS COUNTY OF COLLIN Before me, the undersigned authority, on this day personally appeared Chad Engbrock, of THE WYLIE NEWS, a newspaper regularly published in Collin County, Texas and having general circulation in Collin County, Texas, who being by me duly sworn. deposed and says that the foregoing attached 27/L Legal - Ord. 2001-06 was published in said newspaper on the following dates, to-wit: March 21 , 2001, and , 200 I. ~- Chad ngbrock Subscribed and sworn to before me this the 31 to certify which witness my hand and seal of office. ,2001, Notary Public in and for The State of Texas ~ Serving Wideawake Wylie Since 1947 ORDINANCE NO. 2001-06 AN ORDINANCE OF THE CITY OF WYLIE, TEXAS, ADOPTING THE 1999 EDITION OF THE NATIONAL ELEC- TRICAL CODE AND REPEALING WYLIE ORDINANCE NOS. 94- 53; PROVIDING FOR A PENALTY FOR THE VIOLATION OF THIS ORDINANCE; PROVID- ING FOR REPEALING, SAVINGS AND SEVER- ABILITY CLAUSES; PROVIDING FOR AN EFFECTIVE DATE OF THIS ORDINANCE; AND PROVIDING FOR THE PUBLICATION OF THE CAPTION HERE- nr; JGilll lV!OnUy, ;vwyor Attest: Barbara .';aJinas City Secretary 43-lt-339