Loading...
Ordinance 2009-37 ORDINANCE NO. 2009-37 AN ORDINANCE OF THE CITY OF WYLIE, TEXAS, REPEALING ORDINANCE NO. 2004-22; ADOPTING THE 2006 EDITION OF THE INTERNATIONAL FIRE CODE, SAVE AND EXCEPT THE DELETIONS AND AMENDMENTS SET FORTH HEREIN; AMENDING CHAPTER 46, ARTICLE III (FIRE CODE) OF THE WYLIE CODE OF ORDINANCES; PROVIDING FOR A PENALTY FOR THE VIOLATION OF THIS ORDINANCE; PROVIDING FOR REPEALING, SAVINGS AND SEVERABILITY CLAUSES; PROVIDING FOR AN EFFECTIVE DATE OF THIS ORDINANCE; AND PROVIDING FOR THE PUBLICATION OF THE CAPTION HEREOF. WHEREAS, the City Council of the City of Wylie, Texas ("City Council”) has investigated and determined that it would be advantageous and beneficial to the citizens of the City of Wylie, Texas ("Wylie") to repeal Wylie Ordinance No. 2004-22; and WHEREAS, the City Council has investigated and determined that it would be advantageous and beneficial to amend Chapter 46, Article III (Fire Code) of the Wylie Code of Ordinances; and WHEREAS, the City Council has further investigated and determined that it would be advantageous and beneficial to the citizens of Wylie to adopt the 2006 Edition of the International Fire Code (the "2006 International Fire Code"), save and except the deletions and amendments set forth below. NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF WYLIE, TEXAS: SECTION 1: Findin s Incorporated. The findings set forth above are incorporated into the body of this Ordinance as if fully set forth herein. SECTION 2: Ordinance No. 2004-22 Renealed. Wylie Ordinance No. 2004-22 is hereby repealed in its entirety and replaced by this ordinance. The effective date of the repeal discussed in this Section shall not occur until the effective date of this Ordinance at which time Ordinance No. 2004-22 shall be repealed. Such repeal shall not abate any pending prosecution for violation of the repealed Ordinance No. 2004-22, nor shall the repeal prevent a prosecution from being commenced for any violation if occurring prior to the repeal of Ordinance No. 2004-22. SECTION 3: Adontion of the 2006 International Fire Code. The International Fire Code, 2006 Edition, copyrighted by the International Code Council, Inc., save and except the amendments set forth below, is hereby adopted as the fire code for Wylie, prescribing regulations governing conditions hazardous to life and property from fire, hazardous materials or explosion in the city. The 2006 International Fire Code, save and except the amendments set forth herein, is made a part of this article as if fully set forth herein. One copy of the 2006 International Fire Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 1 5662�3.v1 Code, copyrighted by the International Code Council, Inc., is on file in the office of the Wylie city secretary being marked and designated as the 2006 International Fire Code. SECTION 4: Adopting the 2006 International Fire Code. The 2006 Edition of the International Fire Code as published by the International Code Council is hereby amended as follows by way of additions, deletions and amendments: "ARTICLE III. FIRE CODE Sec. 46-41. Adoption of the 2006 International Fire Code. The International Fire Code, copyrighted by the International Code Council, Inc. save and except the amendments set forth below, is hereby adopted as the fire code for the city, prescribing regulations governing conditions hazardous to life and property from fire, hazardous materials or explosion in the city (the "2006 International Fire Code"). The 2006 International Fire Code, save and except the amendments set forth herein, is made a part of this article as if fully set forth herein. One (1) copy of the 2006 International Fire Code, copyrighted by the International Code Council, Inc., is on file in the office of the city secretary being marked and designated as the 2006 International Fire Code. (Ord. No. 2004-22, 3, 6-5-2004) Sec. 46-42. Amendment to the 2006 International Fire Code. The 2006 International Fire Code is hereby amended as follows: Section 102.4; change to read as follows: 102.4 Application of other codes. The design and construction of new structures shall comply with this code, and other codes as applicable, and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the International Building Code, shall be made in accordance therewith. Section 102.6; Sections 106.2.1 and 106.2.2 change to read as follows: 102.6 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in chapter 45 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between the provisions of this code and the referenced standards, the provisions of this code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 or the ICC Electrical Code shall mean the Electrical Code as adopted. Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 2 566273.v1 Section 106.2; add to read as follows: 106.2.1 Inspection requests. It shall be the duty of the permit holder or their duly authorized agent to notify the fire code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code. 106.2.2 Approval required. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the fire code official. The fire code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the fire code official. Section 202; change definition of "Fire Watch" as follows: Fire watch. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. Section 202; add definitions as follows: Addressable Fire Detection System. Any system capable of providing identification of each individual alarm-initiating device. The identification shall be in plain English and as descriptive as possible to specifically identify the location of the device in alarm. The system shall have the capability of alarm verification. Analog Intelligent Addressable Fire Detection System. Any system capable of calculating a change in value by directly measurable quantities (voltage, resistance, etc.) at the sensing point. The physical analog may be conducted at the sensing point or at the main control panel. The system shall be capable of compensating for long-term changes in sensor response while maintaining a constant sensitivity. The compensation shall have a preset point at which a detector maintenance signal shall be transmitted to the control panel. The sensor shall remain capable of detecting and transmitting an alarm while in maintenance alert. High-rise building. A building having any floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access. Self-service storage,faciliry. Real property designed and used for the purpose of Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'I Fire Code Ordinance Page 3 5662�3.v1 renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. Standby personnel. Qualified fire service personnel, approved by the fire chief. When utilized, the number required shall be as directed by the fire chief. Charges for utilization shall be as normally calculated by the jurisdiction. Section 307.2; change to read as follows: 307.2 Permit required. A permit shall be obtained from the fire code official in accordance with section 105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or open burning. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. Examples of state or local law, or regulations referenced elsewhere in this section may include, but not be limited to, the following: 1. Texas Commission on Environmental Quality guidelines and/or restrictions. 2. State, county or local temporary or permanent bans on open burning. 3. Local written policies as established by the code official. Section 307.4; change to read as follows: 307.4 Location. The location for open burning shall not be less than 300 feet (91 440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet (91 440 mm) of any structure. (exceptions unchanged) Section 307.4.3; add to read as follows: 307.4.3 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with section 307.2. Section 307.5; change to read as follows: 307.5 Attendance. Open burning, trench burns, bonfires or recreational fires shall be constantly attended until the fire is extinguished. A minimum of one portable fire extinguisher complying with section 906 with a minimum 4-A rating or other approved on-site fire-extinguishing equipment, such as dirt, sand, water barrel, garden hose or water truck, shall be available for immediate utilization. Section 308.3.1; change to read as follows: Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 4 566273.v1 308.3.1 Open-flame cooking and 6eating devices. Open-flame cooking devic,�s, charcoal grills, outdoor fireplaces and other similar devices used for cooking, heating or any other purpose shall not be located or used on combustible balconies, decks, or within i 0 feet (3048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings. 2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system. Section 308.3.1.1; change to read as follows: 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. When permitted as listed in the exceptions of section 308.3.1, LP-gas burners having an LP-gas container with a water capacity greater than 2.5 pounds [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within ten feet (3048 mm) of combustible construction. Exceptions: l. One- and two-family dwellings may have containers with a water capacity not greater than 20 pounds (9.08 kg) [nominal 8 pound (3.632 kg) LP-gas capacity] with an aggregate capacity not to exceed 100 lbs (5 containers). 2. Other residential occupancies where buildings, balconies and decks are protected by an approved automatic sprinkler system, may have containers with a water capacity not greater than 20 pounds (9.08 kg) [nominal 8 pound (3.632 kg) LP-gas capacity], with an aggregate capacity not to exceed 401bs (2 containers). Section 401.3; add Section 401.3.4 as follows: 401.3.4 Fire Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given, signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner. Section 405.1; change to read as follows: 405.1 General. Emergency evacuation drills complying with the provisions of this section shall be conducted in the occupancies listed in Table 405.2 or when required by the fire code official. Drills shall be designed in cooperation with the local authorities. Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 5 566273.v1 Section 408.5.4; change to read as follows: 408.5.4 Drill frequency. Emergency evacuation drills shall be conducted at least 12 times per year, four times per year on each shift. Section 503.1.1; add the following sentence to the end of the first paragraph: Except for single- or two-family residences, the path of ineasurement shall be along a minimum of a ten feet wide unobstructed pathway around the external walls of the structure. Section 503.2.1; change to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315mm), except for approved security gates in accordance with section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4267 mm). Exception: Vertical clearance may be reduced provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. Section 503.2.2; change to read as follows: 503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. Section 503.3; change to read as follows: 503.3 Marking. Striping, signs, or other markings, when approved by the code official, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Striping, signs and other markings shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. (1) Striping Fire apparatus access roads shall be continuously marked by painted lines of red traffic paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the striping shall be on the vertical face of the curb. (2) Signs Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 6 566273.v1 be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (6'6") above finished grade. Signs shall be spaced not more than fifty feet (50') apart. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief. Section 503.4; change to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in section 503.2.1 and any area marked as a fire lane as described in section 503.3 shall be maintained at all times. Section 505.1; add to read as follows: 505.1 Address numbers. Approved numerals of a minimum 6" height and of a color contrasting with the background designating the address shall be placed on all new and existing buildings or structures in a position as to be plainly visible and legible from the street or road fronting the property and from all rear alleyways access. Where buildings do not immediately front a street, approved 6 inch height building numerals or addresses and 3-inch height suite apartment numerals of a color contrasting with the background of the building shall be placed on all new and existing buildings or structures. Numerals or addresses shall be posted on a minimum 20 inch by 30 inch background on border. Address numbers shall be Arabic numerals or alphabet letters. The minimum stroke width shall be 0.5 inches. Exception: R-3 Single Family occupancies shall have approved numerals of a minimum 3'h inches in height and a color contrasting with the background clearly visible and legible from the street fronting the property and rear alleyway where such alleyway exists. Section 511 Emergency Radio Communications; add to read as follows: 511.1 Signal strength in buildings. In all new and existing buildings in which the type of construction or distance from an operational emergency services antenna or dispatch site does not provide adequate frequency or signal strength as determined by the code o£ficial, the building owner shall be responsible for providing the equipment, installation and maintenance of said equipment in a manner to strengthen the radio signal. The radio signal shall meet the minimum input output strengths according to the emergency radio system's provider and Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 7 566273.v1 system manager. Section 704.1; change to read as follows: 704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoist ways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, regardless of when constructed, not less than as specified in Table 704.1. When openings are required to be protected, openings into such shafts shall be maintained self-closing or automatic-closing by smoke detection. Existing fusible-link-type automatic door-closing devices are permitted if the fusible link rating does not exceed 135°F (57°C). Section 803.3.2 and Section 803.4.2; add an exception to read as follows: Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with section 903.3.1.1 shall be limited to 50 percent of the wall area. Section 804.1.1; number the existing exception as 1. and add a second exception to read as follows: Exceptions: 1. Trees located in areas protected by approved automatic sprinkler system installed in accordance with section 903.3.1.1 or 903.3.1.2 shall not be prohibited in Groups A, E, M, R-1 and R-2. 2. Trees shall not be prohibited inside private dwelling units of Group R-2 Occupancies. Section 807.4.3.2 and Section 807.4.4.2; add an exception to read as follows: Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. Section 901.6.1; add section to read as follows: 901.6.1.1 Standpipe Testing. Building owners/managers must utilize a licensed fire protection contractor to test and certify standpipe systems. In addition to the testing and maintenance requirements of NFPA 25 applying to standpipe systems, the following additional requirements shall be applied to the testing that is required every 5 years: 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be hydrostatically tested for all FDC's on any type of Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 8 566273.v1 standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the contractor shall connect hose from a fire hydrant or portable pumping system (as approved by the fire code official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. There is no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. 4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's. Contact the Fire Marshal for additional information. 5. Upon successful completion of standpipe test, the contractor shall place a blue tag (as per "Texas Administrative Code, Title 28. Insurance, Part L Texas Department of Insurance, Chapter 34. State Fire Marshal, Subchapter G. Fire Sprinkler Rules, 28 TAC 34.720. Inspection, Test and Maintenance Service (ITM) Tag") at the bottom of each standpipe riser in the building. An example of this tag is located at the end of this SOP. The tag shall be check- marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. 6. The contractor shall follow the procedures as required by "Texas Administrative Code, Title 28. Insurance, Part I. Texas Department of Insurance, Chapter 34. State Fire Marshal, Subchapter G. Fire Sprinkler Rules, 28 TAC" with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (Fire Marshal). 7. Additionally, records of the testing shall be maintained by the owner and contractor, as required by the State Rules mentioned above and NFPA 25. 8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected night time freezing conditions. Ordinance No. 2009-37 Repealing Ordinance No. 2004-2? Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 9 566273.v1 9. Contact the Fire Marshal for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this fire fighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the fire code official. Section 901.7; change to read as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the code official shall be notified immediately and, where required by the code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. Section 902.1; in definition of "Standpipe, Types of', under "manual dry" amend by adding a sentence to the end of "manual dry" to read as follows: The system must be supervised as specified in section 905.2. Section 903.2; amended to delete the exception. Add Section 903.2.8.3 to read as follows: 903.2.8.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. Exception: One-story self-service storage facilities that have no interior corridors, with a one-hour fire barrier separation wall installed between every storage compartment. Section 903.2.10; amend 903.2.10.3 and add 903.2.10.4, 903.2.10.5, and 903.2.10.6 as follows: Amend the title of Section 903.2.10 to read "Windowless stories in all occupancies except R-3 and U". 903.2.10.3 Buildings more than 35 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with section 1509 of the International Building Code, that is located 35 feet (10 668mm) or more above the lowest level of fire department vehicle access. Exception: Open parking structures in compliance with section 406.3 of Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 10 566273.v1 the International Building Code. 903.2.10.4 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see chapter 23 to determine if those provisions apply. 903.2.10.5 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire-extinguishing system. 903.2.10.6 Buildings Over 6,000 sq. ft. An automatic Sprinkler system shall be installed throughout all buildings with a building area over 6,000 sq.ft. For the purpose of this provision, fire walls shall not define separate buildings. Exceptions: l. Open parking garages in compliance with Section 406.3 of the International Building Code. 2. Type A-5. Section 903.3.1.1.1; change to read as follows: 903.3.1.1.1 Exempt locations. When approved by the code official, automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance-rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire- resistance rating of not less than two hours. Section 903.3.5; add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a ten psi Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page i l 566273.v1 safety factor. Section 903.4; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. Section 903.4.2; add second paragraph to read as follows: The alarm device required on the exterior of the building shall be a weatherproof horn/strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. Section 903.6.2; add to read as follows: 903.6.2 Spray booths and rooms. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system in accordance with section 1504. Section 905.2; change to read as follows: 905.2 Installation standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of ten psig and a maximum of 40 psig air pressure with a high/low alarm. Section 905.3.2; delete exceptions #1 and #2. Add Section 905.3.8; and add exception to read as follows: 905.3.8 Building Area. In buildings exceeding 10,000 square feet in area per story, Class I automatic wet ar manual wet standpipes shall be provided where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access. Exception: Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA 14. Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 12 566273.v1 Section 905.4, item #5; amend to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located either on the roof or at the highest landing of stairways with stair access to the roof. An additional hose connection shall be provided at the top of the most hydraulically remote standpipe for testing purposes. Section 905.9; add a second paragraph after the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. Add Section 907.1.3 to read as follows: 907.1.3 Design standards. All alarm systems new or replacement serving 20 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 40 smoke detectors or more than 100 total alarm activating devices shall be analog intelligent addressable fire detection systems. Exception: Existing systems need not comply unless the total building remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% of the building must comply within 18 months of permit application. Section 907.2.1; change to read as follows: 907.2.1 Group A. A manual fire alarm system shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. Section 907.2.3; change to read as follows: 907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100 feet open space, all Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 13 566273.v1 buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. Section 907.2.3; change exception #1 and add exception #l.l to read as follows: 1. Group E educational and day care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler system. 1.1. Residential in-home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see section 907.2.6.) Section 907.2.12; change to read as follows: 907.2.12 High-rise buildings. Buildings having any floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communications system in accordance with section 907.2.12.2 Section 907.2.12, exception #3; change to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with section 303.1 of the International Building Code, when used for open air seating; however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants and similarly enclosed areas. Add Section 907.2.24 and add exceptions to read as follows: 907.2Z4 Mechanical System Smoke Detectors. All commercial air conditioning and heating units shall have an automatic smoke detector installed in the supply air side of all mechanical units installed in a building or space to be utilized for any type of commercial use or occupancy. Exceptions: 1. An additional detection would not be required if the unit is factory manufactured with a smoke detector in return air side. 2. Dedicated exhaust systems. Add Section 907.2.24.1 to read as follows: Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 14 566273.v 1 907.2.24.1 Installation. Smoke detectors requires by this section shall be installed in accordance with NFPA 72. The required smoke detectors shall be installed to monitor the entire airflow conveyed by the system including supply air, return air and/or relief air. Access shall be provided to smoke detectors for inspection and maintenance. Add Section 907.2.24.2 to read as follows: 907.2.24.2 Controls operation. Upon activation, the smoke detectors shall shut down and all operational capabilities of the air distribution system in accordance with the listing and labeling of appliances used in the system. Air distribution systems that are part of a smoke control system shall switch to the smoke control mode upon activation of a detector. Add Section 907.2.24.3 and the exceptions to read as follows: 907.2.24.3 Supervision. The duct smoke detectors shall be connected to a fir alarm system. The actuation of a duct smoke detector shall activate a visible and audible supervisory signal at a constantly attended location. Exceptions: l. The supervisory signal at a constantly attended location is not requires where the duct smoke detector activates the building's alarm —indicating appliances. 2. In occupancies not requires to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Duct smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. Section 907.4; add a second paragaph to read as follows: Manual alarm actuating devices shall be an approved double action type. Add Section 907.6.1 to read as follows: 907.6.1 Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All initiating circuit conductors shall be Class "A" wired with a minimum of six feet separation between supply and return circuit conductors. IDC Class "A" Style D; SLC Class "A" Style 6; NAC Class "B" Style Y. The IDC from an addressable device used to monitor the status of a suppression system may be wired Class B, Style B provided the distance from the addressable device is within 10-feet of the suppression system device. Section 907.9.2; change to read as follows: Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 15 566273.v1 907.9Z High-rise buildings. In buildings that have any floor located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access that are occupied for human occupancy, a separate zone by floor shall be provided for all of the following types of alarm-initiating devices where provided: 1. Smoke detectors. 2. Sprinkler water-flow devices. 3. Manual fire alarm boxes. 4. Other approved types of automatic fire detection devices or suppression systems. Add Section 909.1 to read as follows: 909.1 Scope and Purpose. This section applies to mechanical or passive smoke control systems when they are required for new buildings or portions thereof by provisions of the 2006 International Building Code or this Code. The purpose of this section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. These provisions are not intended for the preservation of contents, the timely restoration of operations, or for assistance in fire suppression or overhaul activities. Smoke control systems regulated by this section serve a different purpose than the smoke- and heat- venting provisions found in Section 910. Mechanical smoke control systems shall not be considered exhaust systems under Chapter 5 of the 2006 International Mechanical Code. Add Section 909.1.1 to read as follows: 909.1.1 Supersession of 2006 International Building Code. This code adoption formally supersedes the amendment to Section 404.1 of the 2006 edition of the International Building Code and restores the original definition of an "Atrium" to read as follows: ATRIUM. Means an opening connecting two or more stories other than enclosed stairways, elevators, hoistways, escalators, plumbing, electrical, air-conditioning and/or other equipment, which is closed at the top and not defined as a"mall." "Stories," as used in this definition, does not include balconies within assembly groups or mezzanines that comply with Section 505 of the 2006 International Building Code. This hereby requires mandatory compliance with Section 404 of the 2006 edition of the International Building Code. Section 910.1; Amend exception 2 to read as follows: Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 16 566273.v1 4. Where areas of buildings are equipped with early suppression fast- response (ESFR) sprinklers, only manual smoke and heat vents shall be required within these areas Section 910.2; Add subsection 910.2.4 and exceptions to read as follows: 910Z.4 Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet (1394 m in single floor area. Exceptions: 1. Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3 and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive materials as required for a high-hazard commodity classification. 3. Buildings of noncombustible construction containing only noncombustible materials. Table 910.3; Change the title of the first row of the table from "Group F-1 and S- 1" to include "Group H" and to read as follows: Group H, F-1 and S-1 Section 910.3.2.2; Add second paragraph to read as follows: The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees (F) (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed. Section 913.1 Add second paragraph and exception to read as follows: When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1. Ordinance No. 2009-37 Repealing Ordinance No. 2004-2? Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 17 566273.v1 Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by Section 506.1. Add Section 1007.2.2 to read as follows: Where elevators are provided in buildings at least one elevator shall be provided for fire department emergency access to all floors. The elevator car shall be of such a size and arrangement to accommodate a 24-inch by 84-inch (610 mm by 1930 mm) ambulance stretcher in the horizontal, open position and shall be identified by the international symbol for emergency medical services (star of life). The symbol shall not be less than 3 inches (76 mm) high and shall be placed inside on both sides of the hoist way door frame. Exceptions must be approved by the Fire Marshal's office. Section 1008.1.3.4; change to add criteria #7 as follows: 7. If a full building smoke detection system is not provided, approved smoke detectors shall be provided on both the access and egress sides of doors and in a location approved by the authority having jurisdiction of NFPA 72. Actuation of a smoke detector shall automatically unlock the door. Section 1017.1; change to add an exception #5 to read as follows: 5. In Group B office buildings, corridor walls and ceilings need not be of fire-resistive construction within office spaces of a single tenant when the space is equipped with an approved automatic fire alarm system with corridor smoke detection. The actuation of any detector shall activate alarms audible in all areas served by the corridor. The smoke-detection system shall be connected to the building's fire alarm system where such a system is provided. Section 1019.1.8; change to read as follows: 1019.1.8 Smoke proof enclosures. In buildings required to comply with section 403 or 405, each of the exits of a building that serves stories where any floor surface is located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access or mare than 30 feet (9144 mm) below the level of exit discharge serving such floor levels shall be a smoke proof enclosure or pressurized stairway in accordance with section 909.20 of the International Building Code. Ordinance No. 2009-37 Repealing Ordinance No. ?004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 18 566273.v1 Section 1020.1.7; change to read as follows: 1020.1.7 Smokeproof enclosures. In buildings required to comply with Section 403 or 405 of the IBC, each of the exits of a building that serves stories where any floor surface is located more than 55 feet (16 764 mm) above the lowest level of fire {remainder of section unchanged}. Section 1028.2; change to read as follows: 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. Section 1504.4; change to read as follows: 1504.4 Fire Protection. New and existing spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system [remainder of section unchanged}. Section 2204.1; change to read as follows: 2204.1 Supervision of dispensing. The dispensing of fuel at motor fuel- dispensing facilities shall be in accordance with the following: 1. Conducted by a qualified attendant; and/or, 2. Shall be under the supervision of a qualified attendant; and/or 3. Shall be an unattended self-service facility in accordance with Section 2204.3. At any time the qualified attendant of item #1 or #2 above is not present, such operations shall be considered as an unattended self-service facility and shall also comply with Section 2204.3. Section 2302; change to add a second paragraph to the definition of "High-Piled Combustible Storage" to read as follows: Any building exceeding 6,000 sq. ft. that has a clear height in excess of 12 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage and shall comply with the provisions of this section. When a specific product cannot be identified, a fire protection system shall be installed as for Class IV commodities, to the m�imum pile height. Table 2306.2; replace text of "footnote j" to read as follows: Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 19 566273.v1 j. Where areas of buildings are equipped with early suppression fast- response (ESFR) sprinklers, only manual smoke and heat vents shall be required within these areas. Add Section 2703.3.1.4.1 as follows: Section 2703.3.1.4.1 Cost Recovery. The city is authorized to clean up, abate or mitigate the effects of any hazardous material deposited upon or into any property or facilities within the limits of the city. Any person causing deposit or failing to provide cleanup, abatement or proper mitigation of such deposits shall be liable for the payment of all costs incurred by the city as a result of such cleanup, abatement or mitigation activity. The remedy provided by this section shall be in addition to any other remedies provided by law. For the purposes of this section, costs incurred by the city shall include, but shall not necessarily be limited to, the following: actual labor costs of city personnel, including, without limitation, workers' compensation benefits, fringe benefits, administrative overhead; costs of equipment operation; costs of materials obtained directly by the city; and cost of any contract labor and materials. Section 3301.1.3; change to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling, assembling, transporting, receiving, keeping, offering and use of fireworks are prohibited. Exception: Only when approved for public fireworks displays, storage and handling of fireworks as provided in section 3304 and 3308 and chapter 46, article IV of the Code of Ordinances. Section 3302; change the definition of "fireworks" to read as follows: Fireworks. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. Section 3308.1; change to read as follows: 3308.1 General. The display of fireworks is prohibited, except as allowed by chapter 46, article IV, section 46-117 of the Code of Ordinances. Section 3403.6; add a second sentence to read as follows: An approved method of secondary containment shall be provided for Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 20 566273.v1 underground tank and piping systems. Section 3404.2.11.5; add a second sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. Section 3404.2.11.5.2; change to read as follows: 3404.2.11.5.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFPA 30 and as specified in section 3404.2.11.5.3. Add Section 3404.2.11.5.3 to read as follows: 3404.2.11.5.3 Dry sumps. Approved sampling tubes of a minimum six inches in diameter shall be installed in the backfill material of each undergound flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling sump at the corners of the excavation with a minimum of four sumps. Sampling tubes shall be placed in the product line excavation within ten feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required. Delete Section 3406.5.4.5 and replace with the following: 3406.5.4.5 Commercial, industrial, governmental or manufacturing. Dispensing of Class II and III motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles located at commercial, industrial, governmental or manufacturing establishments is allowed where permitted, provided such dispensing operations are conducted in accordance with sections 3406.5.4.5.1 through 3406.5.4.5.3. 3406.5.4.5.1 Site requirements. l. Dispensing may occur at sites that have been permitted to conduct mobile fueling. 2. A detailed site plan shall be submitted with each application for a permit. The site plan must indicate: a. All buildings, structures, and appurtenances on site and their use or function; Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 21 566273.v 1 b. All uses adjacent to the property lines of the site; c. The locations of all storm drain openings, adjacent waterways or wetlands; d. Information regarding slope, natural drainage, curbing, impounding and how a spill will be retained upon the site property; and, e. The scale of the site plan. 3. The code official is authorized to impose limits upon: the times and/or days during which mobile fueling operations are allowed to take place and specific locations on a site where fueling is permitted. 4. Mobile fueling operations shall be conducted in areas not generally accessible to the public. 5. Mobile fueling shall not take place within 15 feet (4.572 m) of buildings, property lines, or combustible storage. 3406.5.4.5.2 Refueling operator requirements. 1. The owner of a mobile fueling operation shall provide to the jurisdiction a written response plan which demonstrates readiness to respond to a fuel spill, carry out appropriate mitigation measures, and to indicate its process to properly dispose of contaminated materials when circumstances require. 2. The tank vehicle shall comply with the requirements of NFPA 385 and local, state and federal requirements. The tank vehicle's specific functions shall include that of supplying fuel to motor vehicle fuel tanks. The vehicle and all its equipment shall be maintained in good repair. 3. Signs prohibiting smoking or open flames within 25 feet (7.62 m) of the tank vehicle or the point of fueling shall be prominently posted on three sides of the vehicle including the back and both sides. 4. A fire extinguisher with a minimum rating of 40:BC shall be provided on the vehicle with signage clearly indicating its location. 5. The dispensing nozzles and hoses shall be of an approved and listed type. 6. The dispensing hose shall not be extended from the reel more than 100 feet (30.48m) in length. 7. Absorbent materials, non-water absorbent pads, a ten foot (3.048 m) long containment boom, an approved container with lid, and a non-metallic shovel shall be provided to mitigate a minimum five- gallon fuel spill. 8. Tanker vehicles shall be equipped with a fuel limit switch such as a count-back switch, limiting the amount of a single fueling operation to a maximum of 500 gallons (1893 L) between resettings of the limit switch. Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 22 566273.v1 Exception: Tankers utilizing remote emergency shut-off device capability where the operator constantly carries the shut-off device which, when activated, immediately causes flow of fuel from the tanker to cease. 9. Persons responsible for dispensing operations shall be trained in the appropriate mitigating actions in the event of a fire, leak, or spill. Training records shall be maintained by the dispensing company and shall be made available to the code official upon request. 10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an emergency communications device to notify the proper authorities in the event of an emergency. 3406.5.4.5.3 Operational requirements. 1. The tank vehicle dispensing equipment shall be constantly attended and operated only by designated personnel who are trained to handle and dispense motor fuels. 2. Prior to beginning dispensing operations, precautions shall be taken to assure ignition sources are not present. 3. The engines of vehicles being fueled shall be shut off during dispensing operations. 4. Nighttime fueling operations shall only take place in adequately lighted areas. 5. The tank vehicle shall be positioned with respect to vehicles being fueled so as to preclude traffic from driving over the delivery hose and between the tank vehicle and the motor vehicle being fueled. 6. During fueling operations, tank vehicle brakes shall be set, chock blocks shall be in place and warning lights shall be in operation. 7. Motor vehicle fuel tanks shall not be topped off. 8. The dispensing hose shall be properly placed on an approved reel or in an approved compartment prior to moving the tank vehicle. 9. The code official and other appropriate authorities shall be notified when a reportable spill or unauthorized discharge occurs. Add Section 3803.2.1.8 to read as follows: 3803.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, portable LP-gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20-pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60-pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 23 566273.v1 Section 3804.2; add an exception #2 and #3 to read as follows: 3804.2 Maximum capacity within estabGshed limits. Within the limits established by law restricting the storage of liquefied petroleum gas for the protection of heavily populated or congested areas, the aggregate capacity of any one installation shall not exceed a water capacity of 2,000 gallons (7570 L) (see section 3 of the Sample Ordinance for Adoption of the International Fire Code on page v). Exceptions: 1. In particular installations, this capacity limit shall be determined by the fire code official, after consideration of special features such as topographical conditions, nature of occupancy, and proximity to buildings, capacity of proposed containers, degree of fire protection to be provided and capabilities of the local fire department. 2. Except as permitted in 308.3, 3804.3.2 and exception #3 below, LP-gas containers greater than 25 gallons are not permitted in residential areas. 3. LP-gas containers greater than 60 gallons are not permitted in MH Districts (mobile and manufactured housing), as defined by zoning codes. Add Section 3804.3.2 to read as follows: 3804.3.2 Spas, Pool Heaters and other listed devices. Where natural gas service is not available, LP-Gas containers are allowed to be used to supply spa and pool heaters or other listed devices. Such containers shall be located underground only and may not exceed 250-gallon water capacity. See Table 3804.3 for location of containers. Appendix D, Fire Apparatus Access Roads, is amended as follows: D 103.1 Access Roads with a Hydrant and Figure D 103.1 Dead-end Fire Apparatus Access Road Turnaround. Each reference to "26 feet" or "26' are changed to be "24 feet" or "24' respectively. The reference to "(7925 mm)" is changed to be "(7315 mm)". Table D103.4 Requirements for Dead-end Fire Apparatus Access Roads. Each reference to 20 feet contained in the width column is changed to 24 feet. D103.5 Fire Apparatus Access Road Gates. #1 is amended to read: "1. The minimum gate width shall be 24 feet (7315 mm)." Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 24 566273.v1 Appendices A and C: delete in their entirety Sec. 46-43. Resolution in event of conflicting provisions. To the extent there is any conflict between the International Fire Code and the City of Wylie Water and Sanitary Sewer Design Manual, as amended, the provisions in the Water and Sanitary Sewer Design Manual shall control. (Ord. No. 2004-22, 4, 6-8-2004) Sec.46-44. Penalty. Any person, firm, corporation or business entity violating this article shall be deemed guilty of a misdemeanor, and upon conviction thereof shall be subject to a fine not to exceed the sum of $2,000.00. Each continuing day's violation under this article shall constitute a separate offense. The penal provisions imposed under this article shall not preclude the city from filing suit to enjoin the violation. The city retains all legal rights and remedies available to it pursuant to local, state and federal law. (Ord. No. 2004-22, 10, 6-8-2004) Secs.46-45--46-60. Reserved." SECTION 5: Savin�s/Renealin Clause. All provisions of any ordinance in conflict with this Ordinance are hereby repealed to the extent they are in conflict; but such repeal shall not abate any pending prosecution for violation of the repealed ordinance, nor shall the repeal prevent a prosecution from being commenced for any violation if occurring prior to the repeal of the ordinance. Any remaining portion of conflicting ordinances shall remain in full force and effect. SECTION 6: Penalty Provision. Any person, firm, corporation or business entity violating this Ordinance shall be deemed guilty of a misdemeanor, and upon conviction thereof shall be subject to a fine not to exceed the sum of TWO THOUSAND AND NO/100 DOLLARS ($2,000.00). Each continuing day's violation under this Ordinance shall constitute a separate offense. The penal provisions imposed under this Ordinance shall not preclude Wylie from filing suit to enjoin the violation. Wylie retains all legal rights and remedies available to it pursuant to local, state and federal law. SECTION 7: Severabilitv. If any section, subsection, sentence, clause or phrase of this Ordinance is for any reason, held to be unconstitutional or invalid by a court of competent jurisdiction, such decision shall not affect the validity of the remaining portions of this Ordinance. Wylie hereby declares that it would have passed this Ordinance, and each section, subsection, clause or phrase thereof, irrespective of the fact that any one or more sections, subsections, sentences, clauses, and phrases be declared unconstitutional. Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 25 566273.v1 SECTION 8: Effective Date. This Ordinance shall become effective upon its passage and publication as required by the City Charter and by law. DULY PASSED AND APPROVED by the City Council of the City of Wylie, Texas on this the 26`" day of January 2010. Eric Hogue, M y ATTESTED AND CORRECTLY �F RECORDED: r Carole Ehrlich, ecretary I ,�1887�, Date of publication in The Wvlie News February 3 2010 Ordinance No. 2009-37 Repealing Ordinance No. 2004-22 Adopting the 2006 Edition of the Int'1 Fire Code Ordinance Page 26 566273.v1 C8S Media, Inc. �I�e �armer�biCle �imes Murphy Monitor The Princeton Herald The Sachse News TIIE WYLIE NEWS STATE OF TEXAS COUNTY OF COLLIN Before me, the undersigned authority, on this day personally appeared Chad Engbrock, publisher of The Wylie News, a newspaper regularly published in Collin County, Texas and having general circulation in Collin County, Texas, who being by me duly sworn, deposed and says that the foregoing attached: City of Wylie Ordinance No. 2009-37 was published in said newspaper on the following dates, to-wit: February 3, 2010 Chad Engbrock, Publisher Subscribed and sworn before me on this, the _1�day of 2010 to certify which witness my hand and seal of office. otary P 1' in and for RG Sonia A Duggan The State of Texas My Ccmmission Expires �9,�02/2012 My commission expires Murphy/Sachse/Wylie Office ll0 N. Ballard P.O. Box 369 Wylie, TX 75098 972-442-5515 fax 972-442-4318 Farmersville/Princeton Office 101 S. Main P.O. Box 512 Farmersville, 7'X 75442 972-784-6397 fax 972-782-7023 February 3 4, 2010 ORDINANCE NO. 2009-37 AN ORDINANCE OF THE CITY OF WYLIE, TEXAS, REPEALING ORDI- NANCE NO. 2004- 22; ADOPTING THE 2006 EDITION OF THE INTERNA- TIONAL FIRE CODE, SAVE AND EXCEPT THE DELETIONS AND AMENDMENTS SET FORTH HERE- IN; AMENDING CHAPTER 46, ARTICLE III (FIRE CODE) OF THE WYLIE CODE OF ORDINANCES; PROVIDING FOR A PENALTY FOR THE VIOLATION OF THIS ORDI- NANCE; PROVID- ING FOR REPEAL- ING, SAVINGS AND SEVERABILI- TY CLAUSES; PRO- VIDING FOR AN EFFECTIVE DATE OF THIS ORDI- NANCE; AND PRO- VIDING FOR THE PUBLICATION OF THE CAPTION HEREOF. Eric Hogue, Mayor ATTEST: Carole Ehrlich, City Secretary 38-1t-3399-441�,