Ordinance 2013-06ORDINANCE NO. 2013 -06
AN ORDINANCE OF THE CITY OF WYLIE, TEXAS, REPEALING
ORDINANCE NO. 2012 -33; ADOPTING THE 2012 EDITION OF THE
INTERNATIONAL FIRE CODE, SAVE AND EXCEPT THE
DELETIONS AND AMENDMENTS SET FORTH HEREIN;
AMENDING CHAPTER 46, ARTICLE III (FIRE CODE) OF THE
WYLIE CODE OF ORDINANCES; PROVIDING FOR A PENALTY
FOR THE VIOLATION OF THIS ORDINANCE; PROVIDING FOR
REPEALING, SAVINGS AND SEVERABILITY CLAUSES;
PROVIDING FOR AN EFFECTIVE DATE OF THIS ORDINANCE;
AND PROVIDING FOR THE PUBLICATION OF THE CAPTION
HEREOF.
WHEREAS, the City Council of the City of Wylie, Texas ( "City Council ") has
investigated and determined that it would be advantageous and beneficial to the citizens of the
City of Wylie, Texas ("Wylie") to repeal Wylie Ordinance No. 2012 -33; and
WHEREAS, the City Council has investigated and determined that it would be
advantageous and beneficial to amend Chapter 46, Article III (Fire Code) of the Wylie Code of
Ordinances; and
WHEREAS, the City Council has investigated and determined that it would be
advantageous and beneficial to the citizens of Wylie to adopt the 2012 Edition of the
International Fire Code, save and except the deletions and amendments set forth below (the
"2012 International Fire Code ").
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE
CITY OF WYLIE, TEXAS:
SECTION 1: Findings IncoKporated. The findings set forth above are incorporated into
the body of this Ordinance as if fully set forth herein.
SECTION 2: Repeal of Ordinance No. 2012 -33. Ordinance No. 2012 -33 is repealed in its
entirety and replaced by this Ordinance. The effective date of the repeal discussed in this Section
shall not occur until the effective date of this Ordinance at which time Ordinance No. 2012 -33
shall be repealed. Such repeal shall not abate any pending prosecution and /or lawsuit or prevent
any prosecution and /or lawsuit from being commenced for any violation of Ordinance No. 2012-
33 occurring before the effective date of this Ordinance.
SECTION 3: Adoption of the 2012 International Fire Code. The International Fire Code,
copyrighted by the International Code Council, Inc., is hereby adopted as the Fire Code, save and
except the deletions and amendments set forth in Exhibit "A" attached hereto and incorporated
herein for all purposes, and including Appendix "D" (the "International Fire Code "), prescribing
regulations governing conditions hazardous to life and property from fire, hazardous materials
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 1 of 34
and explosion in the city. The 2012 International Fire Code is made a part of this Ordinance as if
fully set forth herein. One (1) copy of the 2012 International Fire Code is on file in the office of
the City Secretary of Wylie being marked and designated as the 2012 International Fire Code.
SECTION 4: Conflicts. In the event of any conflict between the International Fire Code
and the City of Wylie Water and Sanitary Sewer Design Manual, as amended, the provisions of
the Water and Sanitary Sewer Design Manual shall control.
SECTION 5: Savings/Repealing Clause. All provisions of any ordinance in conflict with
this Ordinance are hereby repealed to the extent they are in conflict; but such repeal shall not
abate any pending prosecution for violation of the repealed ordinance, nor shall the repeal
prevent a prosecution from being commenced for any violation if occurring prior to the repeal of
the ordinance. Any remaining portion of conflicting ordinances shall remain in full force and
effect. A reference in any ordinance to an earlier or different version of a fire code is hereby
amended to refer to the 2012 International Fire Code as it is adopted herein or may be
subsequently amended. However, to the extent there is any conflict between the International
Fire Code and the City of Wylie Water and Sanitary Sewer Design Manual, as amended, the
provisions in the Water and Sanitary Sewer Design Manual shall control.
SECTION 6: Penalty Provision. Any person, firm, corporation or entity violating this
Ordinance shall be deemed guilty of a misdemeanor, and upon conviction thereof shall be
subject to a fine not to exceed the sum of FIVE HUNDRED DOLLARS ($500.00), unless the
violation relates to fire safety, zoning or public health and sanitation, including dumping and
refuse, in which the fine shall not exceed the sum of TWO THOUSAND AND NO /100
DOLLARS ($2,000.00). Each continuing day's violation under this Ordinance shall constitute a
separate offense. The penal provisions imposed under this Ordinance shall not preclude Wylie
from filing suit to enjoin the violation. Wylie retains all legal rights and remedies available to it
pursuant to local, state and federal law.
SECTION 7: Severability. If any section, subsection, sentence, clause or phrase of this
Ordinance is for any reason, held to be unconstitutional or invalid by a court of competent
jurisdiction, such decision shall not affect the validity of the remaining portions of this
Ordinance. Wylie hereby declares that it would have passed this Ordinance, and each section,
subsection, clause or phrase thereof, irrespective of the fact that any one or more sections,
subsections, sentences, clauses, and phrases be declared unconstitutional.
SECTION 8: Effective Date. This Ordinance shall become effective from and after its
adoption and publication as required by law the City Charter and by law.
1
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 2 of 34
DULY PASSED AND APPROVED BY THE CITY COUNCIL OF THE CITY OF
WYLIE, TEXAS, on this 12th day of February, 2013,
ATTESTED TO AND CORRECTLY
RECORDED:
Carofe Ehrlich, CTy Secretary
Date(s) of Publication: February 13, 2013 in the Wylie News.
rA
i
o
OF If >�
r44 OF TEkN-S
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 3 of 34
Exhibit "A"
Amendments to the 2012 International Fire Code
North Central Texas Council of Governments region
The following sections, paragraphs, and sentences of the 2012 International Fire Code are hereby
amended as follows: Standard type is text from the IFC. Underlined type is text inserted. Lined through
type is deleted text from IF
Explanation of Options A, B, and C:
Please note that as there is a wide range in fire fighting philosophies /capabilities of cities across the
region, OPTIONS "A ", "B ", and "C" are provided in the Fire and Building Code amendments. The
City of Wylie hereby adopts Option B.
Section 102.1; change #3 to read as follows:
3. Existing structures, facilities and conditions when required in Chapter 11 or in specific sections of
this code.
(Reason: To clarify that there are other provisions in the fire code applicable to existing buildings that are
not located in Chapter 11, such as Section 55 Premises Identification.)
Section 102.7; change to read as follows:
102.7 Referenced codes and standards. The codes and standards referenced in this code shall be
those that are listed in Chapter 80, and such codes, when specifically adopted, and standards shall be
considered part of the requirements of this code to the prescribed extent of each such reference and as
further regulated in Sections 102.7.1 and 102.7.2.
102.7.1 Conflicts. Where conflicts occur between provisions of this code and referenced codes and
standards, the provisions of this code shall apply.
102.7.2 Provisions in referenced codes and standards. Where the extent of the reference to a
referenced code or standard includes subject matter that is within the scope of this code and any adopted
amendments, the provisions of this code and any adopted amendments, as applicable, shall take
precedence over the provisions in the referenced code or standard.
(Reason: To be consistent with the State of Texas, other referenced codes must be specifically adopted)
Section 105.3.3; change to read as follows:
105.3.3 Occupancy Prohibited before Approval. The building or structure shall not be occupied prior to
the fire code official issuing a permit when required and conducting associated inspections indicating the
applicable provisions of this code have been met.
(Reason: For clarity to allow for better understanding in areas not requiring such permits, such as
unincorporated areas of counties. This amendment may be struck by a city.)
Section 105.7; add Section 105.7.17 to read as follows:
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 4 of 34
105.7.17 Smoke control or exhaust systems. Construction permits are required for smoke control or
exhaust systems as specified in Section 909 and Section 910 respectively. Maintenance performed in
accordance with this code is not considered a modification and does not require a permit.
(Reason: Section 105.7.17 adds construction permit requirements for smoke control and exhaust
systems, which are required fire protection systems by Chapter 9 of the fire code to ensure proper design
and installation of such systems. These changes reflect local practices of municipalities in this region.)
Section 105.7; add Section 105.7.18 to read as follows:
105.7.16 Electronic access control systems. Construction permits are required for the installation or
modification of an electronic access control system, as specified in Section 503 and Section 1008. A
separate construction permit is required for the installation or modification of a fire alarm system that may
be connected to the access control system. Maintenance performed in accordance with this code is not
considered a modification and does not require a permit.
(Reason: Section 105.7.18 adds construction permit requirements for electronic access control systems
for electric security gates and exit doors to ensure proper design and installation of such systems. These
changes reflect local practices of municipalities in this region.)
Section 202; amend and add definitions to read as follows:
[B] AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical,
psychiatric, nursing, or similar care on a less than 24 -hour basis to persons who are rendered incapable
of self - preservation by the services provided. This group may include but not be limited to the following:
- Dialysis centers
- Sedation dentistry
- Surgery centers
- Colonic centers
- Psychiatric centers
(Reason: to clarify the range of uses included in the definition)
[B] ATRIUM. An opening connecting twa three or more stories... {remaining text unchanged}
(Reason: Accepted practice in the region based on legacy codes. IBC Section 1009 permits unenclosed
two story stairways under certain circumstances.)
FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a
building or portion thereof by one or more qualified individuals or standby personnel when required by the
fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of
unwanted fire, raising an alarm of fire and notifying the fire department.
(Reason: Clearly defines options to the fire department for providing a fire watch.)
FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for
entertainment purposes by combustion, deflagration, er detonation, and /or activated by ignition with a
match or other heat producing device that meets the definition of 1 AG fireworks or 1.3G fireworks as set
forth herein. ... {remainder of text unchanged)...
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 5 of 34
(Reason: Increased safety from fireworks related injuries.)
Option A
HIGH -PILED COMBUSTIBLE STORAGE: add a second paragraph to read as follows:
Any building classified as a group S Occupancy or Speculative Building exceeding 12,000 sq.ft. that
has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet,
shall be considered to be high -piled storage.. When a specific product cannot be identified, a fire
protection system and life safety features shall be installed as for Class IV commodities, to the
maximum pile height.
Options B and C
HIGH -PILED COMBUSTIBLE STORAGE: add a second paragraph to read as follows:
Any building classified as a group S Occupancy or Speculative Building exceeding 6,000 sg.ft. that
has a clear height in excess of 14 feet, making it possible to be used for storage in excess of 12 feet,
shall be considered to be high -piled storage. When a specific product cannot be identified, a fire
protection system and life safety features shall be installed as for Class IV commodities, to the
maximum pile height.
(Reason. To provide protection for worst -case scenario in flexible or unknown situations.)
Option A
HIGH -RISE BUILDING. (No Change Required)
Options B and C
HIGH -RISE BUILDING. A building with an occupied floor located more than 75 55 feet (22 660 16 764
mm) above the lowest level of fire department vehicle access.
(Reason To provide a definition that reflects reaional oractices.)
REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles.
This occupancy shall also include garages involved in minor repair, modification and servicing of motor
vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor
part replacement and other such minor repairs.
(Reason: To further clarify types of service work allowed in a repair garage, as well as to correspond with
definition in the IBC.)
SELF - SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or
leasing individual storage spaces to customers for the purpose of storing and removing personal property
on a self - service basis.
(Reason: To provide a definition that does not exist in the code.)
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 6 of 34
STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Chief. When utilized, the
number required shall be as directed by the Fire Chief. Charges for utilization shall be as normally
calculated by the jurisdiction.
(Reason: To provide a definition that does not exist in the code.)
Section 307.1.1; change to read as follows:
307.1.1 Prohibited open burning. Open burning shall bepre#+bited that is offensive or objectionable
because of smoke emissions or when atmospheric conditions or local circumstances make such fires
hazardous shall be prohibited.
Exception: {No change.}
(Reason: Maintains current local requirements based on legacy and 20091FC requirements.)
Section 307.2; change to read as follows:
307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section
105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices,
prevention or control of disease or pests, or open burning a- boa#ire. Application for such approval shall
only be presented by and permits issued to the owner of the land upon which the fire is to be kindled.
Examples of state or local law, or regulations referenced elsewhere in this section may include but not be
limited to the following:
1. Texas Commission on Environmental Quality guidelines and /or restrictions.
2. State, County, or Local temporary or permanent bans on open burning
3. Local written policies as established by the fire code official.
(Reason: Amendments to 307.2, 307.4, 307.4.3, and 307.5 better explain current requirements and
recognize that jurisdictions have local established policies that best fit their environments.)
Section 307.3; change to read as follows_
307.3 Extinguishment authority.
requiFed permit for open buFROR9 has Rot been obtained, the fiFe Gode effiGial is autheFized te erdeF the
The fire code official is authorized to order the
extinguishment by the permit holder, another person responsible or the fire department of open burning
that creates or adds to a hazardous or obiectionable situation.
(Reason: Maintains current local requirements based on legacy and 2009 IFC requirements.)
Section 307.4; change to read as follows_
307.4 Location. The location for open burning shall not be less than 50 300 feet (15 -249 91 440 mm)
from any structure, and provisions shall be made to prevent the fire from spreading to within 50 300 feet
(45-240 91 440 mm) of any structure.
Exceptions: {No change.}
(Reason: Amendments to 307.2, 307.4, 307.4.3 and 307.5 better explain current requirements and
recognize that jurisdictions have local established policies that best fit their environments.)
Section 307.4.3, Exceptions: add exception #2 to read as follows:
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 7 of 34
Exceptions:
2. Where buildings balconies and decks are protected by an approved automatic sprinkler
system.
(Reason: Amendments to 307.2, 307.4, 307.4.3 and 307.5 better explain current requirements and
recognize that jurisdictions have local established policies that best fit their environments.)
Section 307.4.4 and 5; add section 307.4.4 and 307.4.5 to read as follows:
307.4.4 Permanent outdoor firepit. Permanently installed outdoor firepits for recreational fire purposes
shall not be installed within 10 feet of a structure or combustible material.
Exception: Permanently installed outdoor fireplaces constructed in accordance with the
International Building Code.
307.4.5 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with
Section 307.2.
(Reason: Amendments to 307.2, 307.4, 307.4.3 and 307.5 better explain current requirements and
recognize that jurisdictions have local established policies that best fit their environments.)
Section 307.5; change to read as follows:
307.5 Attendance. Open burning, trench burns, bonfires, recreational fires, and use of potable outdoor
fireplaces shall be constantly attended until the... {remainder of section unchanged}
(Reason: Amendments to 307.2, 307.4, 307.4.3 and 307.5 better explain current requirements and
recognize that jurisdictions have local established policies that best fit their environments.)
Section 308.1.1; add sentence to read as follows:
Unmanned free - floatinq devices containing an open flame or other heat source, such as but not limited to
sky lanterns shall be prohibited.
(Reason. Wildland and inherent fire risk presented by allowing an airborne open flame.)
Section 308.1.4; change to read as follows:
308.1.4 Open -flame cooking devices. GhaFGeal buMers and othep 90pen-flame cooking devices,
charcoal grills and other similar devices used for cooking shall not be eperated— located or used on
combustible balconies, decks, or within 10 feet (3048 mm) of combustible construction.
Exceptions:
1. One- and two - family dwellings except that LP -gas containers are limited to a water capacity not
greater than 50 pounds (22.68 kq) [nominal 20 pound (9.08 kg) LP -gas capacityl with an
aggregate LP -gas capacity not to exceed 100 1 b (5 containers).
2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system,
except that LP -gas containers are limited to a water capacity not greater than 50 pounds (22.68
kk) fnominal 20 pound (9.08 kg) LP -gas capacityl with an aggregate LP -gas capacity not to
exceed 40 Ibs (2 containers).
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 8 of 34
3. (No change.)
(Reason: Decrease fire risk in multi - family dwellings and minimizes ignition sources and clarify allowable
limits for 1 & 2 family dwellings, and allow an expansion for sprinklered multi- family uses. This
amendment adds clarification and defines the container size allowed for residences.)
Section 308.1.6.2, Exception #3; change to read as follows:
Exceptions:
3. Torches or flame - producing devices in accordance with Section 3984 308.1.3.
(Reason: Section identified in published code is inappropriate.)
Section 311.5; change to read as follows:
311.5 Placards. Any The fire code official is authorized to require marking of any vacant or abandoned
buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural
or interior hazards, as required by Section 311.5.1 through 311.5.5.
(Reason: There may be situations where placarding is not desired or necessary; also clarifies intent that
it is not the fire code official's responsibility to provide the placard.)
Section 401.9; add Section 401.9 to read as follows:
401.9 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given,
signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner.
(Reason: Places the responsibility on the business or property owner to maintain their fire alarm systems
in approved condition. Allows the enforcement of `prohibition of false alarms ". Replaces text lost from the
1997 Code.)
Section 403.3; change Section 403.3 and add Sections 403.3.1 and 403.3.2 to read as follows:
403.3 Crowd managers. Trained crowd managers shall be provided for facilities or events where mere
tha+; 4;999 250 or more persons congregate. The minimum number of crowd managers shall be
established at a ratio of one crowd manager to every 250 persons. Where appr-Gved by the A% Gode
Exceptions:
1. The number of crowd managers may be reduced by up to fifty percent when, in the
opinion of the code official, the fire protection provided by the facility and the nature of the
event warrant a reduction
2. Assembly occupancies used exclusively for religious worship with an occupant load not
exceeding 1,000.
403.3.1 Training. Training for crowd managers shall be approved and shall be based upon a valid
nob task analysis.
403.3.2 Duties. The duties of crowd managers shall include:
a. An inspection of the area of responsibility to identify and address any egress barriers
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 9 of 34
b. An inspection of the area of responsibility to identify and mitigate any fire hazards
c. Ensure compliance with all permit conditions including those governing pyrotechnics and
other special effects
d. To direct and assist the event attendees in evacuation during an emergency
e. Assist emergency response personnel if requested.
f. Other duties outlined by the Fire Code Official
g. Other duties outlined in the Emergency Plan
(Reason: The published code has no requirement for crowd managers until the occupant load in a public
assembly reaches 1,000, then the code requires five trained crowd managers for an occupant load of
1001. Smaller venues sometimes place the public at greater risk than large ones for many reasons,
including the fact that larger facilities have greater requirements for other fire protection features. The
formatting change to place the potential reduction in the number of crowd managers in an exception is
editorial; the exception was also changed to limit the reduction to half of the required number of crowd
managers. The published code requires "trained crowd managers'; but doesn't provide any guidance or
describe what that training should entail. This has been an ongoing issue for enforcement personnel.)
Section 501.4; change to read as follows:
501.4 Timing of installation. When fire apparatus access roads or a water supply for fire protection is
required to be installed for any structure or development, they shall be installed, tested, and approved
prior to the time of which construction has progressed beyond completion of the foundation of any
structure. , SUGh preteGtiGn shall be installed and made seFViGeable prier te and dwing the tirne Gf
GGnstruGtien eXGept when approved alternative methods of preteGtioR are provided. TemperaFy stree
signs shall be iRstalled at eaGh street intersentien � - A - �hen GGnGtFUGtiGR of new readway6 allows Pa66a9e by
VehiGles in aGGGrdanGe with -2 entann 505 2L.
(Reason: Reflects current practice in the region relative to ensuring fire department and EMS access
during construction, which can be a time of increased frequency for emergency incidents.)
Section 503.1.1; add sentence to read as follows:
Except for one- or two - family dwellings, the path of measurement shall be along a minimum of a ten feet
(10') wide unobstructed pathway around the external walls of the structure.
(Reason: Recognizes that the hose lay provision can only be measured along a pathway that is wide
enough for fire fighter access.)
Section 503.2.1; change to read as follows:
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 28
24 feet (6996 -rte► 7315 mm), exclusive of shoulders, except for approved security gates in accordance
with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet a innhes in 1 16 mm\
14 feet (4267 mm).
Exception: Vertical clearance may be reduced: provided such reduction does not impair access by
fire apparatus and approved signs are installed and maintained indicating the established vertical
clearance when approved.
(Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in firefighting is
increasing in size. The code already recognizes that larger dimensions may be required under Section
503.2.2. The amendments are to standardize the dimensions for this area. With the increase in fire
apparatus size, this will allow for the passage of two fire apparatus during a fire or EMS emergency.)
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 10 of 34
Section 503.2.2; change to read as follows:
503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum
access widths and vertical clearances where they are inadequate for fire or rescue operations.
(Reason: Amendments to 503.2.1 and 503.2.2 recognize that the equipment now used in fire fighting is
increasing in size. The code already recognizes that larger dimensions may be required under Section
503.2.2. The amendments are to standardize the dimensions for this area. With the increase in fire
apparatus size, this will allow for the passage of two fire apparatus during a fire or EMS emergency.)
Section 503.3; change to read as follows:
503.3 Marking. Where required by the fiFe r--n-de
r "" Fkin9" that ORGlude the werd6 NQ PARKING _ FIRE �ANF. Striping, signs, or other markings, when
approved by the fire code official, shall be provided for fire apparatus access roads to identify such roads
or prohibit the obstruction thereof. The rgean6 by whinh fire i -a.,ecS .ere designated Striping, signs and
other markings shall be maintained in a clean and legible condition at all times and be replaced or
repaired when necessary to provide adequate visibility.
(1) Striping — Fire apparatus access roads shall be continuously marked by painted lines of red traffic
paint six inches (6 ") in width to show the boundaries of the lane. The words "NO PARKING FIRE
LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4 ") white letters at 25 feet intervals on
the red border markings along both sides of the fire lanes. Where a curb is available, the striping
shall be on the vertical face of the curb.
(2) Signs — Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be
12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red,
using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the
bottom of the sign shall be six feet, six inches (6'6 ") above finished grade. Signs shall be spaced not
more than fifty feet (50') apart along both sides of the fire lane. Signs may be installed on permanent
buildings or walls or as approved by the Fire Chief.
(Reason. Establishes a standard method of marking and reflects local long- standing practices.)
Section 503.4; change to read as follows:
503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be
obstructed in any manner, including the parking of vehicles. The minimum widths and clearances
established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be
maintained at all times.
(Reason: As originally worded, the section implied that vehicles could be parked in the marked fire lane
and not be in violation if the minimum width is still maintained. Current accepted enforcement practice is
to require the entire marked fire lane to be maintained clear and unobstructed.)
Section 505.1; change to read as follows:
505.1 Address identification. New and existing buildings shall have approved address numbers,
building numbers or approved building identification placed in a position that is plainly legible and visible
from the street or road fronting the property. These numbers shall contrast with their background. Where
required by the fire code official, address numbers shall be provided in additional approved locations to
facilitate emergency response. Address numbers shall be Arabic numbers or alphabetical letters.
Numbers shall be a minimum of 6 inches (152.4 mm) high with a minimum stroke
width of 0.5 inch (12.7 mm). Where access is by means of a private road, buildings do not immediately
front a street, and /or the building cannot be viewed from the public way, a monument, pole or other sign
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 11 of 34
with approved 6 inch (152.4 mm) height building numerals or addresses and 4 inch (101.6 mm) height
suite /apartment numerals of a color contrasting with the background of the building or other approved
means shall be used to identify the structure. Numerals or addresses shall be posted on a minimum 20
inch (508 mm) by 30 inch (762 mm) background on border. Address numbers shall be maintained.
Exception: R -3 Single Family occupancies shall have approved numerals of a minimum 3 '/2
inches (88.9 mm) in height and a color contrasting with the background clearly visible and legible
from the street fronting the property and rear alleyway where such alleyway exists.
(Reason: To increase the minimum addressing requirements for commercial and establish a minimum for
single- family residential.)
Section 507.4; change to read as follows:
507.4 Water supply test date and information. The water supply test used for hydraulic calculation of
fire protection systems shall be conducted in accordance with NFPA 291 "Recommended Practice for Fire
Flow Testing and Marking of Hydrants" and within one year of sprinkler plan submittal. The fire code
official shall be notified prior to the water supply test. Water supply tests shall be witnessed by the fire
code official, as required or approved dGGLIFRentatien of the test shall be provided to the fiFe GGde Offiria4
The exact location of the static /residual hydrant and the
flow hydrant shall be indicated on the design drawings. All fire protection plan submittals shall be
accompanied by a hard copy of the waterflow test report or as approved by the fire code official. The
report must indicate the dominant water tank level at the time of the test and the maximum and minimum
operating levels of the tank as well or identify applicable water supply fluctuation. The licensed
contractor must then design the fire protection system based on this fluctuation information, as per the
applicable referenced NFPA standard. Reference Section 903.3.5 for additional design requirements.
(Reason: Clarifies intent of the test to ensure contractor accounts for water supply fluctuations.)
Section 507.5.4; change to read as follows:
507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. Posts,
fences vehicles growth trash storage and other materials or objects shall not be placed or kept near fire
hydrants fire department inlet connections or fire protection system control valves in a manner that would
prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not
be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants.
(Reason: Maintains wording from 2006 Code to ensure these critical devices are available in an
emergency incident.)
Section 509.1.2; add new Section 509.1.2 to read as follows:
509.1.2 Sign Requirements. Unless more stringent requirements apply, lettering for signs required by
this section shall have a minimum height of 2 inches (50.8 mm) when located inside a building and 4
inches (101.6 mm) when located outside or as approved by the fire code official. The letters shall be of a
color that contrasts with the background.
(Reason: Provides direction as to appropriate sign criteria to develop consistency in this regard.)
Section 603.3.2.1, Exception; change exception to read as follows:
Exception: The aggregate capacity limit shall be permitted to be increased to 3,000 gallons (11,356 L) in
accordance with all requirements of Chapter 57. of Class 11 or III liquid for storage OR pFeteG ed- akhove_-
grGund tanks... (Delete remainder of Exception}
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 12 of 34
(Reason: Change to Section 5704.2.9.5 is included in this amendment package.)
Section 603.3.2.2; change to read as follows:
603.3.2.2 Restricted use and connection. Tanks installed in accordance with Section 603.3.2 shall be
used only to supply fuel oil to fuel - burning or equipment installed in accordance with Section
603.3.2.4. Connections between tanks and equipment supplied by such tanks shall be made using
closed piping systems.
(Reason: Relocate the exception to Chapter 57 for applicability to generator sets, due to contradictory
charging statement in 603.1 to not apply to internal combustion engines. Further, such large quantities of
combustible liquid are more thoroughly addressed in Chapter 57 relative to such tanks.)
Section 604; change to read as follows:
SECTION 604
EMERGENCY AND STANDBY POWER SYSTEMS
604.1 Installation. Emergency and standby power systems required by this code or the International
Building Code shall be installed in accordance with this code, NFPA 110 and 111. Existing installations
shall be maintained in accordance with the original approval, except as specified in Chapter 11.
604.1.1 Stationary generators. Stationary emergency and standby power generators required by
this code shall be listed in accordance with UL 2200.
604.1.2 Critical Operations Power Systems (COPS). For Critical Operations Power Systems
necessary to maintain continuous power supply to facilities or parts of facilities that require
continuous operation for the reasons of public safety, emergency management national security, or
business continuity, see NFPA 70.
604.2 Where required. Emergency and standby power systems shall be provided where required by
Sections 604.2.1 through 604.24 604.2.24 or elsewhere identified in this code or any other referenced
code.
604.2.1 GFQUp A oceupanGies. Emergency voice /alarm communications systems. Emergency
power shall be provided for emergency voice /alarm communications systems in Group the following
occupancies, or as specified elsewhere in this code, in accordance with Section 907.5.2.2.5
907.2.1.1.
Covered and Open Malls, Section 604.2.13
Group A occupancies, Sections 907.2.1.1 and 907.5.2.2.4.
Special Amusement buildings, Section 907.2.12.3
High rise buildings, Section 907.2.13
Atriums, Section 907.2.14
Deep Underground buildings, Section 907.2.19
604.2.2 Smoke control systems. Standby power shall be provided for smoke control systems in the
following occupancies, or as specified elsewhere in this code, in accordance with Section 909.11:
Covered mall building, International Building Code, Section 404.5
Atriums, International Building Code, Section 404.7
Underground buildings, International Building Code, Section 405.5
Group 1 -3, International Buildinq Code, Section 408.9
Stages, International Buildinq Code, Section 410.3.7.2
Special Amusement buildings (as applicable to Group A's), International Building Code, Section
411.1
Smoke protected seating, Section 1028.6.2.1
604.2.3 Exit signs. Emergency power shall be provided for exit signs in accordance with Section
1011.6.3. (90 minutes)
604.2.4 Means of egress illumination. Emergency power shall be provided for means of egress
illumination in accordance with Section 1006.3. (90 minutes)
604.2.5 Accessible means of egress elevators. Standby power shall be provided for elevators that
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 13 of 34
are part of an accessible means of egress in accordance with Section 1007.4.
604.2.6 Accessible means of egress platform lifts. Standby power in accordance with this section
or ASME A18.1 shall be provided for platform lifts that are part of an accessible means of egress in
accordance with Section 1007.5
604.2.7 Horizontal sliding doors. Standby power shall be provided for horizontal sliding doors in
accordance with Section 1008.1.4.3.
604.2.8 Semiconductor fabrication facilities. Emergency power shall be provided for
semiconductor fabrication facilities in accordance with Section 2703.15.
604.2.9 Membrane structures. Emergency power shall be provided for exit signs in temporary tents
and membrane structures in accordance with Section 3103.12.6.1. (90 minutes) Standby power shall
be provided for auxiliary inflation systems in permanent membrane structures in accordance with the
International Building Code. 4 hours
604.2.10 Hazardous materials. Emergency or standby power shall be provided in occupancies with
hazardous materials in accordance with Section 5004.7 and 5005.1.5.
604.2.11 Highly toxic and toxic materials. Emergency power shall be provided for occupancies
with highly toxic or toxic materials in accordance with Sections 6004.2.2.8 and 6004.3.4.2.
604.2 12 Organic peroxides. Standby power shall be provided for occupancies with organic
peroxides in accordance with Section 6204.1.11.
604.2.13 Covered and open mall buildings. (no change).
604.2.14 High -rise buildings. (no change).
604.2.15 Underground buildings. (no change).
604.2.16 Group 1 -3 occupancies. (no change).
604.2.17 Airport traffic control towers. (no change).
604.2.18 Elevators. (no change).
604.2.19 Smokeproof enclosures and Stair Pressurization Alternative. Standby power shall be
provided for smokeproof enclosures stair pressurization alternative and associated automatic fire
detection systems as required by the International Building Code, Section 909.20.6.2.
604.2.20 Elevator pressurization. Standby power shall be provided for elevator pressurization
system as required by the International Building Code, Section 909.21.5.
604.2.21 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be provided
when eliminating the smoke dampers in ducts penetrating shafts in accordance with the International
Building Code, Section 717.5.3, exception 2.3.
604.2.22 Common exhaust systems for clothes dryers. Standby power shall be provided for
common exhaust systems for clothes dryers located in multistory structures in accordance with the
International Mechanical Code Section 504.8, item 7.
604.2.23 Hydrogen Cutoff Rooms. Standby power shall be provided for mechanical ventilation and
gas detection systems of Hydrogen Cutoff Rooms in accordance with the International Building Code,
Section 421.8.
604.2.24 Means of Egress Illumination in Existing Buildings. Emergency power shall be provided
for means of egress illumination in accordance with Section 1104.5 and 1104.5.1 when required by
the fire code official. (90 minutes in 1 -2, 60 minutes elsewhere.)
604 3 Energy time duration. Unless a time limit is specified by the fire code official, in this chapter or
elsewhere in this code or in any other referenced code or standard, the emergency and standby power
system shall be supplied with enough fuel or energy storage capacity for not less than 2 -hour full- demand
operation of the system.
Exception: Where the system is supplied with natural pas from a utility provider and is
approved.
604.3 4 Maintenance. (no change).
604.4 5 Operational inspection and testing. (no change).
604.5 6 Emergency lighting equipment. (no change).
604.5 7 Supervision of maintenance and testing. (no change).
(Reason: These provisions provide a list to complete and match that throughout the codes. IBC Section
2702.13 pyrophoric materials" no longer exists in IFC Section 604. The only new items are the reference
to COPS in NFPA 70, and the specified Energy time duration. Other changes are a reference to a code
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 14 of 34
provision that already exists.)
Section 704.1; change to read as follows:
704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoistways,
service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in
accordance with the codes in effect at the time of construction but, regardless of when constructed, not
less than as required in Chapter 11. New floor openings in existing buildings shall comply with the
International Building Code.
(Reason: Provides standard minimum protection retroactively, but clarifies that this section is not to be
used to reduce higher protection levels that were required when originally constructed.)
Section 807.4.3.2; change to read as follows:
807.4.3.2 Artwork. Artwork and teaching materials shall be limited on the walls of corridors to not more
than 20 percent of the wall area and on the walls of classrooms to not more than 50 percent of each wall
area. Such materials shall not be continuous from floor to ceiling or wall to wall.
Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings
shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be
noncombustible.
(Exception: Corridors protected by an approved automatic sprinkler system installed in accordance
with Section 903.3.1.1 shall be limited to 50 percent of the wall area.
(Reason: Consistent with regional practice. This change allows an increase in wall coverage due to the
presence of sprinklers. Also provides additional guidance relative to acceptable amounts of artwork in
classrooms.)
Section 807.4.4.2; change to read as follows:
807.4.4.2 Artwork. Artwork and teaching materials shall be limited on the walls of corridors to not more
than 20 percent of the wall area and on the walls of classrooms to not more than 50 percent of each wall
area. Such materials shall not be continuous from floor to ceiling or wall to wall.
Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings
shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be
noncombustible.
Exception: Corridors protected by an approved automatic sprinkler system installed in accordance
with Section 903.3.1.1 shall be limited to 50 percent of the wall area.
(Reason: Consistent with regional practice. This change allows an increase in wall coverage due to the
presence of sprinklers. Also provides additional guidance relative to acceptable amounts of artwork in
classrooms.)
Section 901.4.3; change to read as follows:
901,4.3 Fire areas. {First part of section unchanged) ...determined in accordance with Section 707.3.810
of the International Building Code.
(Reason: Incorrect section number is referenced in the published code as 707.3.9, which applies to mixed
use occupancy separation, rather than fire area separation for sprinkler purposes.)
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 15 of 34
Section 901.6.1; add Section 901.6.1.1 to read as follows:
901.6.1.1 Standpipe Testing Building owners /managers must maintain and test standpipe systems as
per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is
required every 5 years:
1. The piping between the Fire Department Connection (FDC) and the standpipe shall be backflushed
when foreign material is present and also hydrostatically tested for all FDC's on any type of
standpipe system Hydrostatic testing shall also be conducted in accordance with NFPA 25
requirements for the different types of standpipe systems.
2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of
flowing water through the standpipe the tester shall connect hose from a fire hydrant or portable
pumping system (as approved by the fire code official) to each FDC and flow water through the
standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm
that there are no open hose valves prior to introducing water into a dry standpipe. There is no
required pressure criteria at the outlet. Verify that check valves function properly and that there are
no closed control valves on the system.
3. Any pressure relief, reducing or control valves shall be tested in accordance with the requirements
of NFPA 25. All hose valves shall be exercised.
4. If the FDC is not already provided with approved caps the contractor shall install such caps for all
FDC's as required by the fire code official.
5. Upon successful completion of standpipe test place a blue tag (as per Texas Administrative Code
Fire Sprinkler Rules for Inspection Test and Maintenance Service (ITM) Tag) at the bottom of
each standpipe riser in the building The tag shall be check - marked as "Fifth Year" for Type of ITM
and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum.
6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow
Tags and Red Tags or any deficiencies noted during the testing, including the required
notification of the local Authority Having Jurisdiction (fire code official) shall be followed.
7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable,
as required by the State Rules mentioned above and NFPA 25.
8. Standpipe system tests where water will be flowed external to the building shall not be conducted
during freezing conditions or during the day prior to expected night time freezing conditions
9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe
systems where employees are not trained in the utilization of this firefighting equipment. All
standpipe hose valves must remain in place and be provided with an approved cap and chain when
approval is given to remove hose by the fire code official.
(Reason: Increases the reliability of the fire protection system and re- emphasizes the requirements of
NFPA 25 relative to standpipe systems, as well as ensuring that FDC connections are similarly
tested /maintained to ensure operation in an emergency incident.)
Section 901.7; change to read as follows:
901.7 Systems out of service. Where a required fire protection system is out of service or in the event
of an excessive number of activations, the fire department and the fire code official shall be notified
immediately and, where required by the fire code official, the building shall either be evacuated or an
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 16 of 34
903.1.1 Alternative protection. Alternative automatic fire - extinguishing systems complying with Section
904 shall be permitted in lieu n addition to automatic sprinkler protection where recognized by the
applicable standard ate, or as approved by the fire code official.
Section 903.2.1.2; No Change.
Option C
Section 903.2.1.2; change to read as follows:
903.2.1.2 Group A -2. An automatic sprinkler system shall be provided for Group A -2 occupancies where
one of the following conditions exists:
1. The fire area exceeds 5;999 4,000 square feet (464-j 39 M2).
2. The fire area has an occupant load of 4W 50 or more.
3. The fire area is located on a floor other than a level of exit discharge serving such
occupancies.
(Reason: Increased fire frequency and severity in A -2 occupancies in recent years, including multi -fire
fatalities in nightclub and restaurant fires, etc.)
Section 903.2.9; add Section 903.2.9.3 to read as follows:
903.2.9.3 Self- service storage facility. An automatic sprinkler system shall be installed throughout all
self - service storage facilities.
Exception: One -story self - service storage facilities that have no interior corridors, with a one -hour fire
barrier separation wall installed between every storage compartment.
(Reason: Fire departments are unable to inspect these commercial occupancies and are unaware of the
contents being stored. This also meets with local practices in the region.)
Option A
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, and 903.2.11.8, as follows:
903.2.11.3 Buildings 55 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level other than penthouses in compliance with Section 1509 of the
International Building Code, that is located 55 feet (16 764
mm) or more above the lowest level of fire department vehicle access.
Exceptions:
1. AmFPGFt GGRtFGl towers.
Open parking structures in compliance with Section 406.5 of the International Building
Code.
3. ^GGUpandes in Group F -'
903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet
(4572 mm) see Chapter 32 to determine if those provisions apply.
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 18 of 34
903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
Protected by an approved automatic fire - extinguishing system.
Option B
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows:
903.2.11.3 Buildings 55 35 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International 8uildinq Code, having aR GGGUpant lead of 30 or mere that is located 55 35 feet (16 764
10 668 mm) or more above the lowest level of fire department vehicle access.
Exceptions:
1 AiFPGFt GGRtFGl tGWeFr,
Open parking structures in compliance with Section 406.5 of the International Building Code.
903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet
(4572 mm), see Chapter 32 to determine if those provisions apply.
903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire - extinguishing system.
903.2.11.9 Buildings Over 6,000 sq.ft. An automatic sprinkler system shall be installed throughout
all buildings with a building area 6,000 scift or greater and in all existing buildings that are enlarged
to be 6,000 sq. ft. or greater. For the purpose of this provision, fire walls shall not define separate
buildings.
Exception: Open parking garages in compliance with Section 406.5 of the International Building
Code.
Option C
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, 903.2.11.9, and 903.2.11.10
as follows:
903.2.11.3 Buildings 55 35 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International Building Code, haviRg an GGGUpant lead Gf 30 or more that is located 55 35 feet (16 764
10 668mm) or more above the lowest level of fire department vehicle access.
Exceptions:
Open parking structures in compliance with Section 406.5 of the International Building Code.
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 19 of 34
3. QGGUpanGie6 in Group F-2.
903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet
(4572 mm) see Chapter 32 to determine if those provisions apply.
903.2.11.8 Spray Booths and Rooms. New and existinq spray booths and spraying rooms shall be
Protected by an approved automatic fire - extinguishing system.
903.2.11.9 Buildings Over 4,000 sq.ft. An automatic sprinkler system shall be installed throughout
all buildings with a building area 4,000 scift or greater and in all existing buildings that are enlarged
to be 4,000 sq ft or greater. For the purpose of this provision fire walls shall not define separate
buildings.
Exception: Open parking garages in compliance with Section 406.5 of the International Building
Code.
903.2.11.10 Expanded tenant spaces. Fire sprinklers shall be installed in all tenant spaces where
the total fire area is 4,000 sq ft or greater. For the purpose of this provision fire walls and /or fire
barriers shall not be used to separate single tenant fire areas.
(Reason: Reflects regional practices.)
Section 903.3.1.1.1; change to read as follows:
903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic sprinklers shall not be
required in the following rooms or areas where such ...(text unchanged}... because it is damp, of fire -
resistance -rated construction or contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire
hazard.
2. Any room or space where sprinklers are considered undesirable because of the nature of the
contents, when approved by the code official.
3. Generator and transformer rooms under the direct control of a public utility, separated from the
remainder of the building by walls and floor /ceiling or roof /ceiling assemblies having a fire -
resistance rating of not less than 2 hours.
5. Fite SePV!Ge aGGess Elevator machine rooms, aad machinery spaces, and hoistways, other than
pits where such sprinklers would not necessitate shunt trip requirements under any
circumstances.
6. {Delete.}
(Reason: Gives more direction to code official. Exception 4 deleted to provide protection where fire risks
are poorly addressed. Amendment 903.2 addresses Exception 5 above relative to the elimination of
sprinkler protection in these areas to avoid the shunt trip requirement.)
Section 903.3.1.2.2; add section to read as follows:
Section 903.3.1.2.2 Attics Open Breezeways, and Attached Garages. Sprinkler protection is required
in attic spaces of such buildings two or more stories in height open breezeways, and attached garages.
(Reason: Open breezeways already require sprinkler protection in Section 1026.6, Exception 4. Attic
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 20 of 34
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 21 of 34
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 22 of 34
AN
Section 907.2.1; change to read as follows:
907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in
accordance with new Section 907.6 shall be installed in Group A occupancies where the having an
occupant load due te the assembly GGGUpanGY i6 of 300 or more persons or more than 100 persons
above or below the lowest level of exit discharge. Group A occupancies not separated from one another
in accordance with Section 707.3.9 of the International Building Code shall be considered as a single
occupancy for the purposes of applying this section. Portions of Group E occupancies occupied for
assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy.
Exception: {No change.)
Exceptions:
1. A manual fire alarm system is not required in Group E educational and day care occupancies
with an occupant load of less than 30 er -less when provided with an approved automatic
sprinkler system.
1.1. Residential In -Home day care with not more than 12 children may use interconnected
single station detectors in all habitable rooms. (For care of more than five children 2 1/2
or less years of age, see Section 907.2.6.)
(Reason: Consistent with Texas State laws concerning day care facility requirements.)
in
Section 907.2.13, Exception 3; change to read as follows:
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 23 of 34
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 24 of 34
910.2 .3 Group H. Buildings and portions thereof used as a Group H occupancy as follows:
'1 In occupancies classified as Group H -2 or H -3, any of which are more than 15,000 square feet
(1394 m) in single floor area.
Exception: Buildings of noncombustible construction containing only noncombustible materials.
2 In areas of buildings in Group H used for storing Class 2 3 and 4 liquid and solid oxidizers Class
1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or
Class 2 or 3 water- reactive materials as required for a high- hazard commodity classification.
Exception: Buildings of noncombustible construction containing only noncombustible materials.
(Reason: Errata — see ICC website for more information - Replaces text from the 2009 IFC that was
accidentally losbleft out of the 2012 edition first printing, as exemplified by the Section number skipping.
Amendment to Section 910.3.2.2 specifies a temperature range at which smoke and heat vents should
activate in sprinklered buildings to ensure that the sprinkler system has an opportunity to activate and
control the fire prior to vent operation.)
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 25 of 34
Section 912.2; add Section 912.2.3 to read as follows:
Chapter 10: Sections 1001 through 1029; replace all references to "fire code official" with
"building official ".
(Reason: Past regional practice and legacy language has always referenced the "building official" as the
authority over Chapter 10 issues, except for the maintenance of the means of egress section. The 2012
edition of the IBC references "building official' in these sections, but references "fire code official' in the
2012 IFC, providing for a direct contradiction when both codes are adopted.)
Section 1004.1.2; delete exception:
1004.1.2 Areas without fixed seating. The number of occupants shall be computed at the rate of one
occupant per unit of area as prescribed in Table 1004.1.2. For areas without fixed seating, the occupant
load shall not be less than that number determined by dividing the floor area under consideration by the
occupant load factor assigned to the function of the space as set forth in Table 1004.1.2. Where an
intended function is not listed in Table 1004.1.2, the fire wde building official shall establish a function
based on a listed function that most nearly resembles the intended function.
eaGh GGGLIpied spaGe, floor oF buildiR9 is designed, although less than there determined—by
GalGUlatiGR, shall be permitted to be, used in the de-teffnination of the design GGG.Upant lead.
(Reason: Authority having jurisdiction (AHJ) already has this authority. Technical substantiation is
required to support deviation from table values.)
Section 1007.1; add the following Exception 4:
Exceptions:
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 26 of 34
u {previous exceptions unchanged}
4. Buildings regulated under State Law and built in accordance with State registered plans, including any
variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of
Section 1007.
(Reason: To accommodate buildings regulated under Texas State Law and to be consistent with
amendments to Chapter 11.)
Section 1007.5; Platform lifts, amend to read as follows:
1007.5 Platform lifts. Platform (wheelchair) lifts ... required accessible route in Section 1109.7 8, Items
1 through 9 10. Standby power. . {remainder unchanged)
(Reason: Editorial.)
Section 1008.1.9.4; amend exceptions 3 and 4 as follows:
Exceptions:
{previous exceptions unchanged)
3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S
Occupancy, {Remainder unchanged)
4. Where a pair of doors serves a Group A B, F, M or S occupancy, {Remainder unchanged)
(Reason: Application to M occupancies reflects regional practice; No. 4 expanded to Group A due to it
being a similar scenario to other uses; No. 4 was regional practice.)
Section 1008.1.9.9; change to read as follows:
1008.1.9.9 Electromagnetically locked egress doors. Doors in the means of egress in buildings with
an occupancy in Group A, B, E, 1 -1, 1 -2, M, R -1 or R -2 and doors to tenant spaces in Group A, B, E, I -1, 1-
2, M, R -1 or R -2 shall be permitted to be electromagnetically locked if equipped with listed hardware that
incorporates a built -in switch and meet the requirements below: {remaining text unchanged)
(Reason: Regional practice to permit such locks due to the presence of trained staff.)
Section 1015; add new section 1015.7 to read as follows:
1015.7 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference the
electrical code as adopted.
(Reason: Cross reference necessary for coordination.)
Section 1016; add new section 1016.2.2 to read as follows:
1016.2.2 Group F -1 and S -1 increase. The maximum exit access travel distance shall be 400 feet (122
m ) in Group F -1 or S -1 occupancies where all of the following are met:
1 The portion of the building classified as Group F -1 or S -1 is limited to one story in he[g
2. The minimum heiqht from the finished floor to the bottom of the ceiling or roof slab or deck is 24
feet (7315 mm): and
3 The building is equipped throughout with an automatic fire sprinkler system in accordance with
Section 903.3.1.1.
(Reason: Past regional practice allowed smoke and heat vents to be utilized to increase travel distance,
which resulted in problems when utilizing ESFR systems. This amendment adopts wording from the
upcoming 2015 IBC, which has been approved by final action via the /CC code development process but
is not yet published.)
Section 1018.1; add exception 6 to read as follows:
Exceptions:
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 27 of 34
(previous exceptions unchanged)
6. In Group B office buildings, corridor walls and ceilings within single tenant spaces need not be of fire -
resistive construction when the tenant space corridor is provided with system smoke detectors tied to an
approved automatic fire alarm. The actuation of any detector shall activate alarms audible in all areas
served by the corridor.
(Reason: To reduce redundant requirements in a single tenant situation. Intended to be consistent with
regional amendment to IFC.)
Section 1018.6; amend to read as follows:
1018.6, Corridor Continuity. Pra-tis; °stanre�rated All corridors shall be continuous from the point of
entry to an exit, and shall not be interrupted by intervening rooms. {Remainder unchanged}
(Exception unchanged)
(Reason: Once in corridor, corridor should not be interrupted or discontinuous.)
Section 1026.6; amend exception 4 to read as follows:
Exceptions:
(previous exceptions unchanged)
4. Separation from the interior open -ended corridors of the building... (remaining text unchanged)
(Reason: To clarify that Section 1022.7, i.e., the 180 degree rule is applicable; and is further reinforced by
new Exception 4.4.)
Section 1028.1.1.1; delete.
(Reason. Unenforceable.)
Section 1029.1; amend to read as follows:
1029.1 General. In addition to the means of egress required by this chapter, provisions shall be made
for emergency escape and rescue openings in Group R and I -1 GFoup R 2 occupancies +a ,assert arise
with Tables 1021.2(i) and 1021 2(2) and Group Q 3 GGGUpannies {Remainder unchanged}
Exceptions:
{Exceptions 1 through 3 unchanged.}
4. In other than Group R -3 occupancies, buildings equipped throughout with an
approved automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2.
(Reason: Maintains legacy language to ensure egress from residential type occupancies and maintain
exception for residential occupancies where an NFPA 13 or 13R sprinkler system is installed, but not for a
13D system.)
Section 1030.2; change to read as follows:
Im�.
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 28 of 34
Section 1103.3;add sentence to end of paragraph as follows:
Provide emergency signage as required by Section 607.2.
(Reason: Coordinates requirements of previous amendment.)
Section 1103.5;add Section 1103.5.3 to read as follows:
1103 5 3 Spray booths and rooms. Existing spray booths and spray rooms shall be protected by an
approved automatic fire-extinguishing system in accordance with Section 2404.
(Reason: Consistent with amendment to IFC 2404, regional practice, and long-standing regional
requirement..)
Section 2304.1;change to read as follows:
2304.1 Supervision of dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be
GGndUGted by a qualified attendant or 6hall be undeF the supervi6ion of a qualified attendant at all tirne6 9
shah be in accordance with SeGtien 2204.3. the following:
1. Conducted by a qualified attendant; and/or,
2. Shall be under the supervision of a qualified attendant; and/or
3. Shall be an unattended self-service facility in accordance with Section 2304.3.
At any time the qualified attendant of item Number 1 or 2 above is not present, such operations shall be
considered as an unattended self-service facility and shall also comply with Section 2304.3.
(Reason: Allows a facility to apply the attended and unattended requirements of the code when both are
potentially applicable.)
Section 2401.2; delete this section.
(Reason: This section eliminates such booths from all compliance with Chapter 15 including, but not
limited to: size, ventilation, fire protection, construction, etc. If the product utilized is changed to a more
flammable substance, the lack of compliance with Chapter 15 could result in significant fire or deflagration
and'subsequent life safety hazard.)
Table 3206.2, footnote j;change text to read as follows:
j. Where areas of buildings are equipped with early
suppression fast-response (ESFR) sprinkler systems Gerdanse with NFIRA 12
sprinklers manual smoke and heat vents or manually activated engineered mechanical smoke
exhaust systems shall be required within these areas.
(Reason: Allows the fire department to control the smoke and heat during and after a fire event, while
ensuring proper operation of the sprinkler protection provided. Also, gives an alternative to smoke and
heat vents.)
40
Ordinance No.2013-06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No.2012-33 Page 29 of 34
1. Only when approved for fireworks displays storage and handling of fireworks as allowed in
Section 5604 and 5608.
2. ManufaGtUre, assembly and te6ting of fireworks a6 allowed On Ser-lien 5-6-0-5.
3-.2. The use of fireworks for approved fireworks displays as allowed in Section 5608.
4. The possession, stGrage, sale... {Delete remainder of text.}
(Reason: Restricts fireworks to approved displays only, which is consistent with regional practice.)
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 30 of 34
5706.5.4.5.1 Site requirements.
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 31 of 34
1. Dispensing may occur at sites that have been permitted to conduct mobile fuelin
2. A detailed site plan shall be submitted with each application for a permit. The site plan must
indicate:
a. all buildings structures, and appurtenances on site and their use or function;
b. all uses adiacent to the property lines of the site;
c. the locations of all storm drain openings, adjacent waterways or wetlands;
d. information regarding slope, natural drainage, curbing, impounding and how a spill will be
retained upon the site property; and,
e. The scale of the site plan.
3. The Code Official is authorized to impose limits upon: the times and /or days during which
mobile fueling operations are allowed to take place and specific locations on a site where
fueling is permitted.
4. Mobile fueling operations shall be conducted in areas not generally accessible to the public.
5. Mobile fueling shall not take place within 15 feet (4.572 m) of buildings, property lines, or
combustible storage.
5706.5.4.5.2 Refueling Operator Requirements.
1. The owner of a mobile fueling operations shall provide to the jurisdiction a written response
plan which demonstrates readiness to respond to a fuel spill, carry out appropriate mitigation
measures and to indicate its process to properly dispose of contaminated materials when
circumstances require.
2. The tank vehicle shall comply with the requirements of NFPA 385 and Local, State and
Federal requirements. The tank vehicle's specific functions shall include that of supplying
fuel to motor vehicle fuel tanks. The vehicle and all its equipment shall be maintained in good
repair.
3. Signs prohibiting smoking or open flames within 25 feet (7.62 m) of the tank vehicle or the
point of fueling shall be prominently posted on 3 sides of the vehicle including the back and
both sides.
4. A fire extinguisher with a minimum rating of 40:13C shall be provided on the vehicle with
signage clearly indicating its location.
5. The dispensing nozzles and hoses shall be of an approved and listed type.
6. The dispensing hose shall not be extended from the reel more than 100 feet (30.48m) in
length.
7. Absorbent materials, non -water absorbent pads, a 10 foot (3.048 m) long containment boom,
an approved container with lid, and a non - metallic shovel shall be provided to mitigate a
minimum 5- gallon fuel spill.
8. Tanker vehicles shall be equipped with a fuel limit switch such as a count -back switch,
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 32 of 34
limiting the amount of a single fueling operation to a maximum of 500 gallons (1893 Q
between resetting of the limit switch.
Exception: Tankers utilizing remote emergency shut -off device capability where the
operator constantly carries the shut -off device which, when activated, immediately
causes flow of fuel from the tanker to cease.
9. Persons responsible for dispensing operations shall be trained in the appropriate mitigating
actions in the event of a fire leak or spill. Training records shall be maintained by the
dispensing company and shall be made available to the fire code official upon request.
10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at
all times an emergency communications device to notify the proper authorities in the event of
an emergency.
5706.5.4.5.3 Operational Requirements.
1. The tank vehicle dispensing equipment shall be constantly attended and operated only by
designated personnel who are trained to handle and dispense motor fuels.
2. Prior to beginning dispensing operations precautions shall be taken to assure ignition
sources are not present.
3. The engines of vehicles being fueled shall be shut off during dispensing operations.
4. Night time fueling operations shall only take place in adequately lighted areas.
5. The tank vehicle shall be positioned with respect to vehicles being fueled so as to preclude
traffic from driving over the delivery hose and between the tank vehicle and the motor vehicle
being fueled.
6. During fueling operations tank vehicle brakes shall be set chock blocks shall be in place and
warning lights shall be in operation.
7. Motor vehicle fuel tanks shall not be topped off.
8. The dispensing hose shall be properly placed on an approved reel or in an approved
compartment prior to moving the tank vehicle.
9. The Code Official and other appropriate authorities shall be notified when a reportable spill or
unauthorized discharge occurs.
(Reason: Provides clarity and organization of the site, operation and use requirements. Maintains long-
standing regional practice.)
so
Section 6103.2.1; add Section 6103.2.1.8 to read as follows:
6103.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not
containers in these situations.)
IM
Section 6104.2, Exception; add an exception 2 to read as follows:
Exceptions:
1_ {existing text unchanged}
2. Except as permitted in 308 and 6104.3.2, LP -gas containers are not permitted in residential
areas.
(Reason: To provide a consistent and reasonable means of regulating the use of portable LP -Gas
containers. References regional amendment to IFC 6104.3.2.)
an
Section 6104.3; add Section 6104.3.2 to read as follows:
6104.3.2 Spas, Pool Heaters and other listed devices. Where natural gas service is not available, an
LP -Gas container is allowed to be used to supply spa and pool heaters or other listed devices. Such
container shall not exceed 250 - gallon water capacity per lot. See Table 6104.3 for location of containers.
Exception: Lots where LP can be off loaded wholly on the property where the tank is located may
install 500 gallon above ground or 1,000 gallon underground approved containers.
(Reason: Allows for an alternate fuel source. Dwelling density must be considered and possibly factored
into zoning restrictions.)
Appendix D
Appendix D, Fire Apparatus Access Roads, is amended as follows:
D103.1 Access Roads with a Hydrant and Figure D103.1 Dead -end Fire Apparatus Access Road
Turnaround. Each reference to "26 feet" or "26' " are changed to be "24 feet" or "24' "
respectively. The reference to "(7925 mm)" is changed to be "(7315 mm) ".
Table D103.4 Requirements for Dead -end Fire Apparatus Access Roads. Each reference to 20
feet contained in the width column is changed to 24 feet.
D103.5 Fire Apparatus Access Road Gates. #1 is amended to read: "1. The minimum gate width
shall be 24 feet (7315 mm)."
Appendices A, B and C: delete in their entirety
END
Ordinance No. 2013 -06 Adopting the 2012 Edition of the International Fire Code
Repealing Ordinance No. 2012 -33 Page 34 of 34
L? ?"!)o jfatofo bi(1, Lntttrc; Murphy MolIitof' I I I e I rincvlon I I ern ltl THE WYHE NEWS
STATE OF TEXAS
COUNTY OF COLLIN
Before me, the undersigned authority, on this day personally appeared Chad Engbrock,
publisher of The Wylie News, a newspaper regularly published in Collin County, Texas
and having general circulation in Collin County, Texas, who being by me duly sworn,
deposed and says that the foregoing attached:
City of Wylie
Ordinance No. 2013 -06
was published in said newspaper on the following dates, to -wit:
February 20, 2013
had Engbrock, Publisher
Subscribed and sworn before me on this, the +h day of , 2013
to certify which witness my hand and seal of office.
—Lo
�`�°� "✓ r`� 13 '�" �x�irF Notary Public in and or
March 21 , 2013 r �'
"` -- - The State of Texas
My commission expires)
RECEIVE
%IutIrh Sach,cW"N11"t)II`i< 1N)N.Wdlard Pr) Box 6)• NN, Ev,Iic.JV'7W)'s•972 1+ MAR 07 2013
,iniwr iiIIc Princeton t)liicc • 101 S 'd • 1' O. 1i, >12 • t armors, III I X ?�I l2 • 9 _ i �ir�r • I_�ti �> -� -tr: *,,.3
Wednesday, February 20, 2013
11!l�ICL�1°,
NO. 2013 -0&
AN ORDINANCE OF
THE CITY OF WYLIE,
TEXAS, REPEALING
ORDINANCE NO.
2012 -33; ADOPTING
THE 2012 EDITION
OF THE INTERNA-
TIONAL FIRE CODE,
SAVE AND EXCEPT
THE DELETIONS
AND AMENDMENTS
SET FORTH HEREIN;
AMENDING CHAP -
TER 46, ARTICLE
III ' (FIRE CODE) OF
THE WYLIE CODE
OF ORDINANCES;
PROVIDING FOR
A PENALTY FOR
THE VIOLATION OF
THIS ORDINANCE;
PROVIDING FOR
REPEALING, SAV-
INGS AND SEVER -
ABILITY CLAUSES;
PROVIDING FOR AN
EFFECTIVE DATE OF
THIS ORDINANCE;
AND PROVIDING
FOR THE PUBLI-
CATION OF THE
CAPTION" HEREOF.
-- 41- -4 -334