Ordinance 2013-08ORDINANCE NO. 2013-08
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF
WYLIE, TEXAS, REPEALING ORDINANCE NO. 2012 -30;
ADOPTING THE 2012 EDITION OF THE INTERNATIONAL
BUILDING CODE FOR COMMERCIAL BUILDINGS, SAVE AND
EXCEPT THE DELETIONS AND AMENDMENTS SET FORTH
HEREIN; AMENDING ARTICLE III (BUILDING CODE) OF
CHAPTER 22 (BUILDINGS AND BUILDING REGULATIONS) OF
PART II OF THE WYLIE CODE OF ORDINANCES; PROVIDING
FOR A PENALTY FOR THE VIOLATION OF THIS ORDINANCE;
PROVIDING FOR REPEALING, SAVINGS AND SEVERABILITY
CLAUSES; PROVIDING FOR AN EFFECTIVE DATE OF THIS
ORDINANCE; AND PROVIDING FOR THE PUBLICATION OF THE
CAPTION HEREOF.
WHEREAS, the City Council of the City of Wylie, Texas ( "City Council ") has
investigated and determined that it would be advantageous and beneficial to the citizens of the
City, of Wylie, Texas ( "Wylie ") to repeal Wylie Ordinance No. 2012 -30; and
WHEREAS, the City Council has investigated and determined that it would be
advantageous and beneficial to amend Article III (Building Code) of Chapter 22 (Buildings and
Building Regulations) of Part II of the Wylie Code of Ordinances; and
WHEREAS, the City Council has investigated and determined that it would be
advantageous and beneficial to the citizens of Wylie to adopt the 2012 Edition of the
International Mechanical Code for commercial buildings, save and except the deletions and
amendments set forth below (the "2012 International Building Code for Commercial
Buil dins ").
NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE
CITY OF WYLIE, TEXAS:
SECTION 1: Findings Incolporated. The findings set forth above are incorporated into
the body of this Ordinance as if fully set forth herein.
SECTION 2: Ordinance No. 2012 -30 Repealed. Wylie Ordinance No. 2012 -30 is
repealed in its entirety and replaced by this Ordinance. The effective date of the repeal discussed
in this Section shall not occur until the effective date of this Ordinance at which time Ordinance
No. 2012 -30 shall be repealed. Such repeal shall not abate any pending prosecution and /or
lawsuit or prevent any prosecution and /or lawsuit from being commenced for any violation of
Ordinance No. 2012 -30 occurring before the effective date of this Ordinance.
SECTION 3: Adoption of the 2012 International Building Code For Commercial
Buildings. The 2012 International Building Code for Commercial Buildings, copyrighted by the
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 1
623113.1
International Code Council, Inc., save and except the amendments set forth in Exhibit "A ",
attached hereto and incorporated herein for all purposes ( "2012 International Building Code for
Commercial Buildings "), is hereby adopted, prescribing regulations applicable to all commercial
or nonresidential structures and existing premises and constitutes minimum requirements and
standards for construction applications. The 2012 International Building Code for Commercial
Buildings is made a part of this Ordinance as if fully set forth herein. One (1) copy of the 2012
International Building Code for Commercial Buildings is on file in the office of the City
Secretary of Wylie being marked and designated as the 2012 International Building Code for
Commercial Buildings.
SECTION 4: Amendment to Article III (Building Code) of Chapter 22 (Buildings and
Building Regulations) of Part II of the Wylie Code of Ordinances. Article III (Building Code) of
Chapter 22 (Buildings and Building Regulations) of Part II of the Wylie Code of Ordinances, is
hereby amended to reflect the adoption of the 2012 International Building Code for Commercial
Buildings, including any amendments set forth in Exhibit "A ".
SECTION 5: Savings/Repealing C lause. All provisions of any ordinance in conflict with
this Ordinance are hereby repealed to the extent they are in conflict; but such repeal shall not
abate any pending prosecution for violation of the repealed ordinance, nor shall the repeal
prevent a prosecution from being commenced for any violation if occurring prior to the repeal of
the ordinance. Any remaining portion of conflicting ordinances shall remain in full force and
effect. A reference in any ordinance to an earlier or different version of a building code is
hereby amended to refer to the 2012 International Building Code for Commercial Buildings as it
is adopted herein or may be subsequently amended.
SECTION 6: Penalty Provision. Any person, firm, corporation or entity violating this
Ordinance shall be deemed guilty of a misdemeanor, and upon conviction thereof shall be
subject to a fine not to exceed the sum of FIVE HUNDRED AND NO /100 DOLLARS
($500.00), unless the violation relates to fire safety, zoning or public health and sanitation,
including dumping and refuse, in which the fine shall not exceed the sum of TWO THOUSAND
AND NO /100 DOLLARS ($2,000.00). Each continuing day's violation under this Ordinance
shall constitute a separate offense. The penal provisions imposed under this Ordinance shall not
preclude Wylie from filing suit to enjoin the violation. Wylie retains all legal rights and
remedies available to it pursuant to local, state and federal law.
SECTION 7: Severability. If any section, subsection, sentence, clause or phrase of this
Ordinance is for any reason, held to be unconstitutional or invalid by a court of competent
jurisdiction, such decision shall not affect the validity of the remaining portions of this
Ordinance. Wylie hereby declares that it would have passed this Ordinance, and each section,
subsection, clause or phrase thereof, irrespective of the fact that any one or more sections,
subsections, sentences, clauses, and phrases be declared unconstitutional.
SECTION 8: Effective Date. This Ordinance shall become effective from and after its
adoption and publication as required by the City Charter and by law.
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 2
623113.1
DULY PASSED AND APPROVED BY THE CITY COUNCIL OF THE CITY OF
WY'LIE, TEXAS, on this 26th day of February 2013.
ATTESTED AND CORRECTLY
RECORDED:
fri
Carole Ehrlich, ecretary
Date(s) of Publication: March 6, 2013, in the Wylie News
OF� IV
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings
623113.1
Page 3
EXHIBIT "A"
Local Amendments to the
2012 International Building Code
The following sections, paragraphs, and sentences of the 2012 International Building Code are hereby
amended as follows: Standard type is text from the IBC. Underlined type is text inserted. Lined thr.,ugI
type is deleted text from IF?L
Explanation of Options A. B and C:
Please note that as there is a wide range in fire - fighting philosophies / capabilities of cities across the
region, OPTION "A ", OPTION "B" and OPTIION "C" are provided in the Fire and Building Code
amendments. Jurisdictions should choose one or the other based on their fire - fighting philosophies /
capabilities when adopting code amendments. The City of Wylie hereby adopts Option B.
Section 109; add Section 109.7, 109.7.1, 109.7.2 and 109.8 to read as follows:
109.7 Work without a permit.
109.7.1 Investigation Whenever work for which a permit is required by this code has been
commenced without first obtaining a permit a special investigation shall be made before a permit
may be issued for such work.
109.7.2 Fee An investigation fee in addition to the permit fee shall be collected whether or not a
permit is subsequently issued The investigation fee shall be equal to the amount of the permit fee
required by this code or the city fee schedule as applicable The payment of such investigation fee
shall not exempt the applicant from compliance with all other provisions of either this code or the
technical codes nor from penalty prescribed by law.
109.8 Unauthorized cover up fee Any work concealed without first obtaining the required inspection in
violation of Section 110 shall be assessed a fee as established by the city fee schedule.
(Reason: This fee is not a fine or penalty but is designed to compensate for time and to remove incentive
to attempt to evade permits and code compliance. Text taken from former Uniform Administrative Code.)
Section 110.3.5; jurisdiction has the option to delete depending on local inspection policies.
Lath or gvpsum board inspections are not normally performed in this area
Section 202; amend definition of Ambulatory Care Facility to read as follows:
AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical,
psychiatric, nursing or similar care on a less than 24 -hour basis to individuals who are rendered incapable
of self - preservation by the services provided. This group may include but not be limited to the following:
- Dialysis centers
- Sedation dentistry
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 4
623113.1
Surgery centers
Colonic centers
.-Psychiatric centers
(Reason: To clarify the range of uses included in the definition. (Explanatory note related to Ambulatory
Care Facilities: This group of uses as defined in Chapter 2 includes a medical or dental office where
persons are put under for dental surgery or other services. Section 903.2.2 will now require such uses to
be sprinklered if on other than the floor of exit discharge or if four or more persons are put under on the
level of exit discharge. Recommend (1.) jurisdictions document any pre- existing non- conforming
conditions prior to issuing a new C of O for a change of tenant and, (2.) On any medical or dental office
specify on C of O the maximum number of persons permitted to be put under general anesthesia.
It is recommended that before a Certificate of Occupancy is issued, a letter of intended use from the
business owner shall be included and a C of O documenting the maximum number of care recipients
incapable of self - preservation allowed.)
Section 202; add definition of Assisting Living Facilities to read as follows.
ASSISTED LIVING FACILITIES.A building or part thereof housing persons, on a 24- hourbasis, who
because of age, mental disability or other reasons, live in a supervised residential environment which
provides personal care services. The occupants are capable of responding to an emergency situation
without physical assistance from staff.
(Reason: The code references Assisted Living facilities and definition was deleted)
_... .. q y"s ar� i�����, ,
Section 202; amend definition of "Atrium" to read as follows:
ATRIUM. An opening connecting two -three or more stories... {Balance remains unchanged}
(Reason: Accepted practice in the region based on legacy codes. Section 1009 permits unenclosed two
story stairways under certain circumstances.)
h.. d
Oil 5 ` y z + 2 N x, M °�, 4` y ,. ' 2. =,F k`: k 'z+�y .a • s +
Option A
Section 202; {No amendment necessary}
Option B
Section 202; amend definition to read as follows:
HIGH -RISE BUILDING. A building with an occupied floor located more than 7555 feet (22 860
mm)(16 764 mm) above the lowest level of fire department vehicle access.
(Reason: To define high -rise, as it influences sprinkler requirement thresholds based on the fire - fighting
capabilities of a jurisdiction. This correction needed for Option B cities only as a basic definition of High
Rise is now provided.)
s � W. �3
W
s.
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 5
623113.1
Section 303.1.3; add a sentence to read as follows:
303.1.3 Associated with Group E occupancies. A room or space used for assembly purposes that is
associated with a Group E occupancy is not considered a separate occupancy except when applying the
assembly requirements of Chapter 10 and 11.
(Reason: To clarify that egress and accessibility requirements are applicable for assembly areas, i.e.
ca_ feteria, auditoriums, etc.)
aq
�.
. �� r
Section 304.1; add the following to the list of occupancies:
Fire stations
Police stations with detention facilities for 5 or less
Consistent with regional practice dating back to the
Section 307.1; add the following sentence to Exception 4:
4. Cleaning establishments... {text unchanged} ...with Section 707 or 1 -hour horizontal assemblies
constructed in accordance with Section 711or both. See also IFC Chapter 12 Dry Cleaning Plant
provisions.
(Reason: To call attention to detailed requirements m the Ftre Code )
a . � . l .4.,, � ., . „. . ... .. t
Section 403. 1, Exception 3; amended to read as follows:
1. {existing unchanged}
2. {existing unchanged{
3. Open air portions of buildings+egs with a Group A -5 occupancy in accordance with
Section 303.6.
4. {existing unchanged)
5. {existing unchanged}
(Reason To clarify enclosed portions are not exempt.)
..'` .
Section 403.3, Exception; delete exception #2.
1. {existing unchanged}
2. Delete
To ,provide adequate fire protection to enclosed
Section 404.5; delete exception.
(Reason: Consistent with amended atrium definition.)
r f MITI,
Section 406.3.2; add item 3 to read as follows:
1. {existing unchanged}
2. {existing unchanged{
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 6
623113.1
3. A separation is not required between a Group R -2 and U carport provided that the carport is
entirely open on all sides and that the distance between the two is at least 10 feet (3048 mm)
(Reason: Simplifies the fire separation distance and eliminates the need to obtain opening information on
existing buildings when adding carports in existing apartment complexes. Consistent with legacy codes in
effect in region for years and no record of problems with car fires spreading to apartments as a result.)
Section 406.8; add a second paragraph to read as follows:
This occupancy shall also include garages involved in minor repair, modification and servicing of motor
vehicles for items such as lube changes inspections windshield repair or replacement shocks minor
part replacement and other such minor repairs.
(Reason: To further clarify types of service work allowed in a repair garage, as well as to correspond with
definition in the IFC.)
0.� AM
tR�k ' 4¢' 3 ti..',.''', K e'' x a° a a fi •'* syF �.^ :'.. i "i
Oate,. ,�
Section 506.2.2; add sentence to read as follows:
506.2.2 Open Space Limits. Such open space shall be either on the same lot or dedicated for public use
and shall be accessed from a street or approved fire lane. In order to be considered as accessible, if not
in direct contact with a street or fire lane, a minimum 10 -foot wide pathway meeting fire department
access from the street or approved fire lane shall be provided.
(Reason: To define what is considered accessible. Consistent with regional amendment to IFC 504. 1.)
Section 509.3; Delete Section
Section 712.1.8, amend item 5 to read as follows:
1. {existing unchanged)
2. (existing unchanged)
3. {existing unchanged)
4. {existing unchanged)
5. Is not open to a corridor in Group I and RH occupancies.
6. {existing unchanged)
7. (existing unchanged)
(Reason: To be consistent with regionally accepted practices.)
Section 713.14.1 Elevator Lobby. Exceptions: 4.3 amended to read as follows:
Option A
Section 713.14.1; Exception 4.3 {No amendment necessary}
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 7
623113.1
E n B on 713.14.1; Exception 4.3 Elevators serving floor levels over 7-555 feet (" °�m) 1(6 764
bove the lowest level of fire department vehicle access in high rise buildings.
(Reason: This correction needed for Option B cities only as a basic definition of High Rise is now
provided.)
$ m `,b #W£a,'i
Section 903.1.1; amended to read as follows:
[F] 903.1.1 Alternative protection. Alternative automatic fire - extinguishing systems complying with
Section 904 shall be permitted in lieu of addition to automatic sprinkler protection where recognized by
the applicable standard aad, or as approved by the fire code official.
(Reason. Such alternative systems do not provide the reliability of automatic sprinkler protection in
general. An applicant could pursue an Alternate Method request to help mitigate the reliability issues with
these alternative systems with the fire code official if so desired, or there may be circumstances in which
the fire code official is acceptable to allowing an alternate system in lieu of sprinklers, such as kitchen
hoods or paint booths This also meets with local practices in the region.)
Section 903.2; add the following:
[F] 903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall
be provided in the locations described in Sections 903.2.1 through 903.2.12. Automatic Sprinklers shall
not be installed in elevator machine rooms elevator machine spaces and elevator hoist ways, other than
pits where such sprinklers would not necessitate shunt trip requirements under any circumstances.
Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry
doors to the elevator machine room indicating "ELEVATOR MACHINERY — NO STORAGE ALLOWED."
(Reason: Firefighter and public safety. This amendment eliminates the shunt trip requirement of the
International Building Code Section 3006.5 for the purpose of elevator passenger and firefighter safety.
This amendment is contingent on the Building Code amendment eliminating the Exceptions to Section
3006.4, such that passive fire barriers for these areas are maintained. This also meets with local practices
in the region.)
,moo.. ry "ti
N 011 101, 0
Section 903.2; delete the exception.
(Reason: The exception deletion is due to the fact that such telecom areas pose an undue fire risk to the
structural integrity of the building. This also meets with local practices in the region.)
Section 903.2.9; add Section 903.2.9.3 to read as follows:
[F] 903.2.9.3 Self- service storage facility. An automatic sprinkler system shall be installed throughout
all self - service storage facilities.
Exception: One -story self - service storage facilities that have no interior corridors, with a one -hour fire
barrier separation wall installed between every storage compartment.
(Reason: Fire departments are unable to inspect these commercial occupancies and are unaware of the
contents being stored. This also meets with local practices in the region.)
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 8
623113.1
Option A
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, and 903.2.11.8, as follows:
[F] 903.2.11.3 Buildings 55 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International Building Code, that is located 55 feet (16 764
mm) or more above the lowest level of fire department vehicle access.
Exceptions:
2-0pen parking structures in compliance with Section 406.5 of the Buildinq Code.
903.2.11.7 High -Piled Combustible Storage For any building with a clear height exceeding 12 feet
(4572 mm), see IFC Chapter 32 to determine if those provisions apply.
903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be
protected by an approved automatic fire - extinguishing system.
Option B
Section 903.2.11; change 903.2.11.3 and add 903.2.11.7, 903.2.11.8, and 903.2.11.9 as follows:
903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed
throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the
International Building Code, that is located 5535 feet (4-6
76410 668mm) or more above the lowest level of fire department vehicle access.
Exceptions:
1. AaFp()Ft GentFel towers.
–Open parking structures in compliance with Section 406.5 of the International Building Code.
3. OGGUpanGies in GFoup F-22.
903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet
(4572 mm), see IFC Chapter 32 to determine if those provisions apply.
903.2.11.8SPray Booths and Rooms New and existing spray booths and spraying rooms shall be
Protected by an approved automatic fire - extinguishing system.
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 9
623113.1
903.2.11.9 Buildings Over 6,000 sq. ft. An automatic sprinkler system shall be installed throughout
all buildings with a building area over 6,000sq.ft. For the purpose of this provision, fire walls shall
not define separate buildings.
Exception: Open parking garages in compliance with Section 406.5 of the International Building
Code.
(Reason: Reflects regional practices.)
Section 903.3.1.1.1; amended to read as follows:
[F] 903.3.1.1.1 Exempt locations. When approved by the fire code official, automatic sprinklers shall not
be required in the following rooms or areas where such ...(text unchanged}... because it is damp, of fire -
resistance -rated construction or contains electrical equipment.
1. Any room where the application of water, or flame and water, constitutes a serious life or fire
hazard.
2. Any room or space where sprinklers are considered undesirable because of the nature of the
contents, when approved by the code official.
3. Generator and transformer rooms under the direct control of a public utility, separated from the
remainder of the building by walls and floor /ceiling or roof /ceiling assemblies having a fire -
resistance rating of not less than 2 hours.
4. In moms or areas that are Of RonGGrnbustmble GGRGtFUGtien with wholly nOnGOrnbuStible GGntents.
5. Fire ss°^^^° a^^° °° Elevator machine rooms, machinery spaces, and hoist ways, other than pits
where such sprinklers would not necessitate shunt trip requirements under any circumstances.
6. {Delete.}
(Reason: Gives more direction to code official. Exception 4 deleted to provide protection where fire risks
are poorly addressed. Amendment 903.2 addresses Exception 5 above relative to the elimination of
sprinkler protection in these areas to avoid the shunt trip requirement.)
Section 903.3.1.2.2; add the following:
[F]Section 903.3.1.2.2 Attics, Open Breezeways, and Attached Garages. Sprinkler protection is
required in attic spaces of such buildings two or more stories in height, open breezeways, and attached
garages.
(Reason: Open breezeways already require sprinkler protection in Section 1026.6, Exception 4. Attic
protection is required in accordance with existing regional practice and issues with fire exposure via soffit
vents, as well as firefighter safety. Attached garages already require sprinkler via NFPA 13R — re-
emphasis.)
Section 903.3.1.3; add the following:
[F]903.3.1.3 NFPA 13D sprinkler systems. Automatic sprinkler systems installed in one- and two- family
dwellings, Group R -3 and R-4 congregate living facilities and townhouses shall be permitted to be
installed throughout in accordance with NFPA 13D or in accordance with state law.
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 10
623113.1
(Reason: To allow the use of the Plumbing section of the IRC and recognize current state stipulations in
this regard.)
MW MAUMMUS
Section 903.3.5 Water Supplies; add a second paragraph to read as follows:
jFlWater supply as required for such systems shall be provided in conformance with the supply
requirements of the respective standards; however, every fire protection system shall be designed with a
10 psi safety factor. Reference Section IFC 507.4 for additional design requirements.
(Reason: To define uniform safety factor.) IN
tMM
JIM
Section 903.4 Sprinkler system supervision and alarms; add a second paragraph after the
exceptions to read as follows:
IFlSprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the
sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All
control valves in the sprinkler and standpipe systems except for fire department hose connection valves
shall be electrically supervised to initiate a supervisory signal at the central station upon tampering
(Reason. To avoid significant water losses. Consistent with amendment to IFC 905.9.)
6 � � �.,5 `"','�jj'+i ;* .i:" £: ¢. S ',+�.� .# 3si �� k sz# 5 „.y .c fi 5�4,v � k edtr ""wk •i&;.
Section 903.4.2 Alarms; add second paragraph to read as follows:
WIThe alarm device required on the exterior of the building shall be a weatherproof horn /strobe
notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire
department connection.
(Reason: Fire department connections are not always located at the riser,, this allows the fire department
faster access.)
Section 905.2 Installation standard; amended to read as follows:
LF1905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and
NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum
of 40 psis air pressure with a high /low alarm.
(Reason: To define manual dry standpipe supervision requirements. Helps ensure the integrity of the
standpipe system via supervision, such that open hose valves w i l l result i n a supervisory low air alarm.)
... '`� _�' " t ,#Uy
Add Section 905.3.9 and exception to read as follows:
W1905.3.9 Building area. In buildings exceeding 10,000 square feet in area per story, Class I automatic
wet or manual wet standpipes shall be provided where any portion of the building's interior area is more
than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department
vehicle access.
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 11
623113.1
Exception: Automatic dry and semi - automatic dry standpipes are allowed as provided for in NFPA
14.
Allows for the rapid deployment of hose lines to the body of the fire.
Section 905.4, item 5; change to read as follows:
I. {existing unchanged)
2. {existing unchanged)
3. {existing unchanged}
4. {existing unchanged}
[F]5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3 - percent
slope), each standpipe shall be provided with a two-way a-hose connection shall be located to
serve the roof or at the highest landing of a stairway with stair access to the roof provided in
accordance with Section 1009.16.An additional hose connection shall be provided at the top of
the most hydraulically remote standpipe for testing purposes.
6. {existing unchanged}
(Reason: Maintains previously adopted amendment for the following purpose. Reduced the amount of
)ressure reauired to facilitate testing, and provides backup protection for fire fighter safety)
Section 905.4 Location of Class 1 standpipe hose connections; add the following item7:
[F]7 When required by this Chapter, standpipe connections shall be placed adiacent to all required exits
to the structure and at two hundred feet (200') intervals along major corridors thereafter.
Allows for the rapid deployment of hose lines to the body of the
Section 905.9 Valve supervision; add a second paragraph after the exceptions to read as follows:
[F]Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the
sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All
control valves in the sprinkler and standpipe systems except for fire department hose connection valves
shall be electrically supervised to initiate a supervisory signal at the central station upon tampering.
To avoid significant water losses. Consistent with amendment to IFC 903.4
Add Section 907.1.4 to read as follows:
fFl 907.1.4 Design standards All alarm systems new or replacement shall be addressable. Alarm
systems serving more than 20 smoke detectors shall be analog addressable.
Exception: Existing systems need not comply unless the total building remodel or expansion
initiated after the effective date of this code as adopted exceeds 30% of the building. When cumulative
building remodel or expansion exceeds 50% of the building must comply within 18 months of permit
application.
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 12
623113.1
(Reason: Consistent with local practice and emerging technology. Reduces need for panel replacement in
the future.)
Id`s IX- Ali'..g...°^
Section 907.2.1; amended to read as follows:
[F] 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in
accordance with new Section 907.6 shall be installed in Group A occupancies having an occupant load of
300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group
A occupancies not separated from one another in accordance with Section 707.3.9 of the International
Building Code shall be considered as a single occupancy for the purposes of applying this section.
Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm
system as required for the Group E occupancy.
Exception: {unchanged.}
Activation of fire alarm notification appliances shall:
1.Cause illumination of the means of egress with light of not less than 1 foot - candle (11 lux) at the
walking surface level, and
2. Stop any conflicting or confusing sounds and visual distractions.
(Reason: Increases the requirement to be consistent with Group B requirement. Also addresses issue
found in Group A occupancies of reduced lighting levels and other AN equipment that distracts from fire
alarm notification devices Also pi reflects regional practice.)
.�. , c.��lr xse atx�. ,a x. �5,at... ... ;,wE�m: i.�7 +b..s� xsi ', „n,`r ��c
Section 907.2.3; amended to read as follows:
[F] 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an
emergency voice /alarm communication system meeting the requirements of Section 907.5.2.2 and
installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When
automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be
connected to the building fire alarm system. An approved smoke detection system shall be installed in
Group E day care occupancies. Unless separated by a minimum of 100' open space all buildings
whether portable buildings or the main building will be considered one building for alarm occupant load
consideration and interconnection of alarm systems.
(Reason: To distinguish educational from day care occupancy minimum protection requirements. Further,
to define threshold at which portable buildings are considered a separate building for the purposes of
alarm s stems )
... .
Section 907.2.3; add exception 1.1 to read as follows:
[F] Exceptions:
1. A manual fire alarm system is not required in Group E educational and day care occupancies
with an occupant load of 30 or less when provided with an approved automatic sprinkler
system.
1.1. Residential In -Home day care with not more than 12 children may use interconnected
single station detectors in all habitable rooms. (For care of more than five children 2 1/2
or less years of age, see Section 907.2.6.)
(Reason Consistent with Texas State laws concerning day care facility requirements.)
': ._t z r.
o v . «� i.. } .x 3 s£ ,{ �, f :v14 `f 'kM -3v47 b�lyh'v'TJu
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 13
623113.1
to reduce false alarms. Consistent with
Add Section 907.6.1.1 to read as follows:
M 907.6.1.1 Wiring Installation All fire alarm systems shall be installed in such a manner that a failure
of any single initiating device or single open in an initiating circuit conductor will not interfere with the
normal operation of other such devices All signaling line circuits (SLC) shall be installed in such a way
that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and
return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits
and shall have a minimum of four feet separation horizontal and one foot vertical between supply and
return circuit conductors The initiating device circuit (IDC) from an addressable input (monitor) module
may be wired Class B provided the distance from the addressable module to the initiating device is ten
feet or less.
(Reason. To provide uniformity in system specifications and guidance to design engineers. Improves
reliability of fire alarm devices and systems.)
Add Section 907.6.5.3 to read as follows:
fFl 907.6.5.3 Communication requirements All alarm systems new or replacement, shall transmit
alarm supervisory and trouble signals descriptively to the approved central station remote supervisory
station or proprietary supervising station as defined in NFPA 72 with the correct device designation and
location of addressable device identification Alarms shall not be permitted to be transmitted as a General
Alarm or Zone condition.
(Reason: To assist responding personnel in locating the emergency event.)
Section 910.1; change Exception 2 to read as follows: {existing unchanged}
[F]2. Where areas of buildings are equipped with early suppression fast - response (ESFR)
sprinklers, autematiGonly manual smoke and heat vents shall Abe required within these areas.
Automatic smoke and heat vents are prohibited.
Allows the fire department to control the smoke and heat during and after a fire event.
Section 910.2 Where required to read as follows:
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 14
623113.1
[F] { -fext unchanged) ...... Sections 910.2.1 aPA-through 910.2.24
Added numbers 910.2.3 and 910.2.
Add subsections 910.2.3 with exceptions to read as follows:
FF1 910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows:
1. In occupancies classified as Group H -2 or H -3, any of which are more than 15,000 square feet
(1394 m) in single floor area.
Exception: Buildings of noncombustible construction containing only noncombustible materials
2. In areas of buildings in Group H used for storing Class 2 3 and 4 liquid and solid oxidizers Class
1 and unclassified detonable organic peroxides Class 3 and 4 unstable (reactive) materials or
Class 2 or 3 water- reactive materials as required for a high- hazard commodity classification
Exception: Buildings of noncombustible construction containing only noncombustible materials
(Reason: Provides an acceptable alternative for large storage and manufacturing occupancies, rather
than requiring interior rated exit passageways, as has been allowed for many years.)
, WMIM 0 MAN 0 ,
Add' subsections 910.2.4 to read as follows:
[Fl 910.2.4 Exit access travel distance increase. Buildings and portions thereof used as a Group F -1 or
S -1 occupancy where the maximum exit access travel distance is increased in accordance with Section
1016.2.2.
(Reason: Provides an acceptable alternative for large storage and manufacturing occupancies, rather
than re uirin Jnterior rated exit passa eways as has been allowed for man ears
Table 910.3; Change the title of the first row of the table from "Group F -1 and S-1" to include
"Group H" and to read as follows:
Group H F -1 and S -1
with the amendment 910.2.3 to include Groun H.
Add Section 912.2.3 to read as follows:
jF1 912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 feet of the fire
department connection as the fire hose lays along an unobstructed path
(Reason Consistent with regional practices.)
`P
Section 913.1; add second paragraph and exception to read as follows:
jFFlWhen located on the ground level at an exterior wall the fire pump room shall be provided with an
exterior fire department access door that is not less than 3 ft. in width and 6 ft — 8 in in height regardless
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 15
623113.1
of any interior doors that are provided A key box shall be provided at this door, as required by IFC
Section 506.1.
Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior
wall the corridor leading to the fire pump room access from the exterior of the building shall be
provided with equivalent fire resistance as that required for the pump room, or as approved by the fire
code official Access keys shall be provided in the key box as required by IFC Section 506.1.
(Reason: This requirement allows fire fighters safer access to the fire pump room. The requirement
allows access without being required to enter the building and locate the fire pump room interior access
door during a fire event. The exception recognizes that this will not always be a feasible design scenario
for some buildings, and as such, provides an acceptable alternative to protect the pathway to the fire
pump room.)
Section 1007.1; add the following Exception 4:
Exceptions:
1. {existing unchanged)
2. {existing unchanged}
3. {existing unchanged}
4. Buildings regulated under State Law and built in accordance with State registered plans, including
any variances or waivers granted by the State shall be deemed to be in compliance with the
requirements of Section 1007.
(Reason: To accommodate buildings regulated under Texas State Law and to be consistent with
amendments to Chapter 11)
. �' N�y��' a...:. >.u.. .,
Section 1007.5; Platform lifts, amended to read as follows:
1007.5 Platform lifts. Platform (wheelchair) lifts ... required accessible route in Section 1109. -78, Items
1 through 1310. Standby power. {remainder unchanged}
(Reason Editorial.) tn M h11,4�..
Section 1008.1.9.4; amend exceptions 3 and 4 as follows:
Exceptions:
1. {existing unchanged}
2. {existing unchanged)
3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S
occupancy. {Remainder unchanged)
4. Where a pair of doors serves a Group A, B, F, M or S occupancy. {Remainder unchanged)
5. {existing unchanged}
Reason: Application to M occupancies reflects regional practice; No. 4 expanded to Group
A due to it being a similar scenario to other uses No 4 was regional practice
NO
Section 1008.1.9.9; change to read as follows:
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 16
623113.1
1008.1.9.9 Electromagnetically locked egress doors. Doors in the means of egress in buildings with
an occupancy in Group A, B, E, 1 -1, 1 -2, M, R -1 or R -2 and doors to tenant spaces in Group A, B, E, I -1. I-
2 M, R -1 or R -2 shall be permitted to be electromagnetically locked if equipped with listed hardware that
incorporates a built -in switch and meet the requirements below: {remaining text unchanged}
(Reason Regional practice to permit such locks due to the presence of trained staff)
Section 1015; add new section 1015.7 to read as follows:
1015.7 Electrical Rooms. For electrical rooms special exiting requirements may apply. Reference the
electrical code as adopted.
(Reason: Cross reference necessary for coordination.)
Section 1016; add new section 1016.2.2 to read as follows:
1016.2.2 Roof Vent Increase. In buildings that are one story in height equipped with automatic heat and
smoke roof vents complying with Section 910 and equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1, the maximum exit access travel distance shall be 400 feet
for occupancies in Group F -1 or S -1.
(consistent with regional practice)
a«w.� �t':'+ '..E �` " Ift 1 ON
Section 1018.1; add exception 6 to read as follows:
1. lexisting unchanged}
2. lexisting unchanged)
:3. {existing unchanged}
4. {existing unchanged}
h. {existing unchanged)
6. In Group B office buildings, corridor walls and ceilings within single tenant spaces need not be of
fire - resistive construction when the tenant space corridor is provided with system smoke
detectors tied to an approved automatic fire alarm. The actuation of anv detector shall activate
alarms audible in all areas served by the corridor
(Reason: To reduce redundant requirements in a single tenant situation. Intended to be consistent with
regional amendment to IFC.
Section 1018.6; amended to read as follows:
1018.6, Corridor Continuity. Fire- ResistanGe4 ;4 All corridors shall be continuous from the point of
entry to an exit, and shall not be interrupted by intervening rooms. {Remainder unchanged}
Exception unchangedl
(Reason: Once in corridor, corridor should not be interrupted or discontinuous.)
Section 1026.6; amended exception 4 to read as follows:
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 17
623113.1
Exceptions: {Exceptions 1 through 3 unchanged)
4. Separation from the +rimier open -ended corridors of the building... {remaining text unchanged)
(Reason: To clarify that Section 1022.7, i.e., the 180 degree rule is applicable; and is further reinforced by
new Exception 4 4 )
IQ
Section 1028.1.1.1; delete.
(Reason: Unenforceable.)
Section 1101.2; Add exception to read as follows:
Exceptions: Projects registered with the Architectural Barriers Division of the Texas Department of
Licensing and Regulation shall be deemed to be in compliance with the requirements of this Chapter.
(Reason: To accommodate buildings regulated under state law.)
Table 1505.1; delete footnote c and replace footnote b with the following:
a. {existing unchanged}
b. Non - classified roof coverings shall be permitted on buildings of U occupancies having not more
than 120 sq. ft. of protected roof area. When exceeding 120 sq. ft. of protected roof area,
buildings of U occupancies may use non -rated non - combustible roof coverings.
G. [delete]
(Reason: Conforms to regional practice affording increased fire protection.)
Section 1505.7; delete the section
(Reason: Conforms to regional practice.)
Section 1510.1; add a sentence to read as follows:
1510.1 General. Materials and methods of applications used for recovering or replacing an existing roof
covering shall comply with the requirements of Chapter 15. All individual replacement shingles or shakes
shall be in compliance with the rating required by Table 1505.1.
{text of exception unchanged)
(Reason: Relocated the text to more appropriate place. Previously was footnote "b" to Table 1505.1)
Section 2901.1; add a sentence to read as follows:
[P] 2901.1 Scope. (existing text to remain) The provisions of this Chapter are meant to work in
coordination with the provisions of Chapter 4 of the International Plumbing Code. Should any conflicts
arise between the two chapters the Building Official shall determine which provision applies.
(Reason: Gives building official discretion.)
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 18
623113.1
azt
Section 2902.1; add a second paragraph to read as follows:
In other than E Occupancies, the minimum number of fixtures in Table 2902.1 may be lowered if
_requested in writing, by the applicant stating reasons for a reduced number and approved by the Building
Official.
(Reason: To allow flexibility for designer to consider specific occupancy needs.)
Table 2902.1; amended footnote f to read as follows:
a. {existing unchanged)
b. {existing unchanged)
C. (existing unchanged)
d. {existing unchanged)
e. {existing unchanged)
f. Drinking fountains are not required in M Occupancies with an occupant load of 100 or less, B
Occupancies with an occupant load of 25 or less, and for dining and /or drinking
establishments.
g {existing unchanged)
Section 2902.1.3; add new Section 2902.1.3 to read as follows:
2902.1.3 Additional fixtures for food preparation facilities. In addition to the fixtures required in this
Chapter, all food service facilities shall be provided with additional fixtures set out in this section.
2902.1.3.1 Hand washing lavatory. At least one hand washing lavatory shall be provided for use by
employees that is accessible from food preparation, food dispensing and ware washing areas. Additional
hand washing lavatories may be required based on convenience of use by employees.
2902.1.3.2 Service sink. In new or remodeled food service establishments, at least one service sink or
one floor sink shall be provided so that it is conveniently located for the cleaning of mops or similar wet
floor cleaning tool and for the disposal of mop water and similar liquid waste. The location of the service
sink(s) and /or mop sink(s) shall be approved by the <Jurisdiction's> health department.
Section 3006.1; amended to read as follows:
3006.1, General. Assess Elevator machine rooms shall be provided. (Remainderunchanged.)
(Reason: An elevator machine room is necessary to provide a protected space for elevator equipment
that ,is used by the fire service the disabled and in the future building occupant evacuations )
V WIN
Section 3006.4 {3006.5 if previous amendment adopted }; add a sentence to read as follows and
delete exceptions 1 and 2:
LFj 3006.4. Machine Rooms and Machinery Spaces: (text unchanged) ... Storage shall not be allowed
within the elevator machine room. Provide approved signage at each entry door to the elevator machine
room stating "Elevator Machinery— No Storage Allowed."
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 19
62311.3.1
(Reason: Firefighter and public safety. This amendment eliminates the shunt trip requirement of the
International Building Code Section 3006.5 for the purpose of elevator passenger and firefighter safety.
This amendment is contingent on the Building Code amendment eliminating the Exceptions to Section
3006.4, such that passive fire barriers for these areas are maintained. This also meets with local practices
m the re ion.
Section 3109.1; amended to read as follows:
3109.1 General. Swimming pools shall comply with the requirements of sections 3109.2 through 3109.5
and other applicable sections of this code; adopted ISPSC and complying with applicable state laws.
To recognize adopted International Swimming Pool & Spa Code and `state
Section 3401.65 Alternative Compliance. Work performed in accordance with the International Existing
Building Code shall be deemed to comply with the provisions of this chapter with prior approval from the
Building Official.
(Reason: Correct typo and align with referenced standards) y
ix 3 A -M
** *3401.6 Alternative Compliance to 3401.5
** *3401.5 Dangerous Conditions to 3401.6
(Reason: Correct typo and align with referenced standards.)
.��,:° > ;. »• �;? l° aid �'°sx.a', Y. � 4 '�', -t^3 'i- ,.`.� � `� u� � 'Y „*�`�,,dTM,x� �� � ,�' s fir; }�.? : ;px '� �-. *�,�.
k' . ._ ���'��"✓,� Y����3byq''�'�' r>Y``M'' nand, .,'r,.:r�,!�.�+„s#�r„u?.�i„`y+i ,.. .: ._ �t.,... �. ^,'.: �_8`. ���'
Chapter 23 Wood; add to read as follows;
The most current lumber span Tables available from the "AMERICAN WOOD COUNCIL" will be the
reference standard for lumber used in span rate applications in all wood construction within THE CITY OF
WYLIE The "AWC" Span Tables will replace span tables published in the "first printing" of the 2012
International Building Code The substitution due to deficiencies in actual span limits as revealed during
destructive testing by the "Southern Pine Inspection Bureau" on 2 x 4 Southern Yellow Pine No. 2, No. 3
Construction Standard and Utility grades The "American Wood Council' Span Tables will replace the
following 2012 International Building Code Tables.
2308.8(1)
Page
479/480
2308.8(2)
Page
481/482
• 2308.10.2(1)
Page
493/494
• 2308.10.2(2)
Page
495/496
2308.10.3(1)
Page
497/498
• 2308.10.3(2)
Page
499/500
• 2308.10.3(3)
Page
501/502
2308.10.3(4)
Page
503/504
• 2308.10.3(5)
Page
505/506
• 2308.10.3(6)
Page
507/508
Ordinance No. 2013 -08
Repealing Ordinance No. 2012 -30
Adopting the 2012 Edition of the International Building Code for Commercial Buildings Page 20
623113.1
TOO 'I'll Illet biliv 2t unc • :Murphy Monitor • The. Princeton I Jerald THE WYLIE NEWS
media
STATE OF TEXAS
COUNTY OF COLLIN
Before me, the undersigned authority, on this day personally appeared Chad Engbrock,
publisher of The Wylie News, a newspaper regularly published in Collin County, Texas
and having general circulation in Collin County, Texas, who being by me duly sworn,
deposed and says that the foregoing attached:
City of Wylie
Ordinances 2013 -K 2o13-�i, 2o13-t012o13•Il, Zo13 -t21
was published in said newspaper on the following dates, to -wit: Zp 13 . t3 , 2013 -1S
March 6, 2013
Chad Engbrock, Publisher
�
Subscribed and sworn before me on this, the a-
_day of fflovl� '2013
to certify which witness my hand and seal of office.
RE
APR 0 4 3
._ My COMMISSION EXPIRES
wch 21, 2017
Notary Public in an for
The State of Texas
My commission expires
M rulihN 5ach c ;WV Iic ()II`icc • I ION. P,alIard • P.O. Boy : ;o9 • WN,Iit% ( X 75098 • 972.442..5515 • larx 972 442 4; 18
1 Arnwr,v iI1.7Princeton (Micc • 101 S. Mam • II,O. Bov 512 • hiI rile] s -iIIe, hX 75442 • 97' 784 -6397 • 1'.tx 972 782- 7(}2,;
ORDIN ANCE
N0.2013-08
AN ORDINANC
OF THE CITY
COUNCIL OF THE
CITY OF WYLIE,
TEXAS, REPEAL-
ING ORDINANCE
NO. 2012 -30;
ADOPTING THE
2012 EDITION OF
THE INTERNA-
TIONAL BUILD-
ING . CODE FOR
COMMERCIAL
BUILDINGS, SAVE
AND EXCEPT THE
DELETIONS AND
AMENDMENTS
SET FORTH
HEREIN; AMEND-
ING ARTICLE III
(BUILDING CODE)
OF CHAPTER 22
(BUILDINGS AND
BUILDING REG-
ULATIONS) OF
PART II OF THE
WYLIE CODE OF
ORDINANCES;
PROVIDING , FOR
A PENALTY FOR
THE VIOLATION
OF THIS ORDI-
NANCE; PROVID-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL-
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS OR-
DINANCE; AND
PROVIDING FOR
THE PUBLICA-
TION OFTHE CAP -
MN HEREOF.
ORDINANCE
NO. 2013-"
AN ORDINANCE
OF THE CITY
COUNCIL OF THE
CITY OF WYLIE,
TEXAS, REPEAL-
ING ORDINANCE
NO. 2012 -34,
ADOPTING THE
2012 EDITION
OF THE INTER-
NATIONAL FUEL
GAS CODE FOR
COMMERCIAL
BUILDINGS, SAVE
AND EXCEPT THE
DELETIONS AND
AMENDMENTS
SET FORTH HERE-
IN; AMENDING
ARTICLE XXII
(INTERNATIONAL
FUEL GAS CODE)
OF CHAPTER 22
(BUILDINGS AND
BUILDING REG-
ULATIONS) OF
PART H OF THE
WYLIE CODE OF
ORDINANCES;
PROVIDING FOR
A PENALTY FOR
THE VIOLATION
OF THIS ORDI-
NANCE; PROVID-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL-
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS OR-
DINANCE; AND
PROVIDING FOR
THE PUBLICA-
TION OF THE CAP-
TION HEM.
ORDINANO
NO. 2013-10
AN ORDINANCE
OF THE CITY
COUNCIL OF
THE CITY OF
WYLIE, TEXAS,
REPEALING OR-
DINANCE NO.
2012 -35; ADOPT
ING THE 2012
EDITION OF THE
INTERNATIONAL
MECHANICAL
CODE FOR COM-
MERCIAL BUILD-
INGS, SAVE AND
EXCEPT THE DE-
LETIONS AND
AMENDMENTS
SET FORTH HERE -
IN; AMENDING
ARTICLE V (ME-
CHANICAL CODE)
OF CHAPTER 22
(BUILDINGS AND
BUILDING REG-
ULATIONS) OF
PART II OF THE
WYLIE CODE
OF ORDINANCE;
PROVIDING FOR
A PENALTY FOR
THE VIOLATION
OF THIS ORDI-
NANCE; PROVID-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL-
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS OR-
DINANCE; AND
PROVIDING FOR
THB PUBLICA-
TiON OF THE CAP -
TIM HEREOF.
ORMANCE
NO. 2013-11
AN ORDINANCE
OF THE CITY
COUNCIL OF THE
CITY OF WYLIE,
TEXAS, REPEAL-
ING ORDINANCE
NO. 2012 -36;
ADOPTING THE
2012 EDITION OF
THE INTERNA-
TIONAL PLUMB-
ING CODE FOR
COMMERCIAL
BUILDINGS, SAVE
AND EXCEPT
THE DELETIONS
AND AMEND-
MENTS . SET
FORTH HEREIN;
AMENDING ARTI-
CLE IV (PLUMB-
ING CODE) OF
CHAPTER 22
(BUILDINGS AND
BUILDING REG-
ULATIONS) OF
PART H OF THE
WYLIE CODE OF
ORDINANCES;
PROVIDING FOR
A PENALTY FOR
THE VIOLATION
OF THIS ORDI-
NANCE; 'PROVID-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL-
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS OR-
DIN NCE; AND
PROVIDING
THE P CA-
TIO CAP -
TI�SN HEREOF.
2C March 6 - 7, 2013
ORDINANCE
NO. 2013-12
AN ORDINANCE
OF THE CITY
COUNCIL OF
THE CITY OF
WYLIE, TEXAS,
REPEALING OR-
DINANCE NO.
2012 -38; ADOPT-
ING THE 2012
EDITION OF THE
INTERNATIONAL
RESIDENTIAL
CODE FOR RESI-
DENTIAL BUILD-
INGS, SAVE AND
EXCEPT THE DE-
LETIONS AND
AMENDMENTS
SET FORTH
HEREIN; AMEND-
ING ARTICLE
XIX (INTERNA-
TIONAL RESI-
DENTIAL CODE)
OF CHAPTER 22
(BUILDINGS AND
BUILDING REG-
ULATIONS) OF
PART II OF THE
WYLIE CODE OF
ORDINANCES;
PROVIDING FOR
A PENALTY FOR
THE VIOLATION
OF THIS ORDI-
NANCE; PROVID-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL-
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS OR-
DINANCE; AND
PROVIDING FOR
THE PUBLICA-
TION OF THE CAP-
TION HEREOF.
OANCE
NO X13`13
AN ORDINANCE
OF : THE CITY
COUNCIL OF THE
CITY OF WYLIE,
TEXAS, :REPEAL -
ING ORDINANCE
NO. 2012 -40;
ADOPTING_ THE
20i f EDITION OF
THE NATIONAL
ELECTRIC CODE
FOR
CL4LL J-
DENTIAL BUILD-
INGS, SAVE
AND EXCEPT
THE- . DELETIONS.
AND AmEND-
MENTS SET
NTH HEREIN;
AMENDING AR-
TICLE VII (ELEC-
TRICAL CODE)
OF CI3A . R 22
(BUILDINGS AND
BUILDING , REG-
ULATIONS) OF
PART II OF THE
WYLIE CODE OF
ORDINANCES;
PROVIDING FOR
A PENALTY FOR
TAE VIOLATION
OF THIS ORDI
NANCE, PROVID-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL_
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS OR-
DINANCE; AND
PROVIDING FOR
THE PUBLICA-
TION 4FT'HE CAS'•.
TION . HERF.
OEANCE
N0.1013.15
AN ORDINANCE
OF THE CITY OF
WYLIE, TEXAS,
AMENDING EX-
HIBIT "A OF OR-
DINANCE NO.
2010 -20 (CON-
SOLIDATED FEE
ORDINANCE)
AND SECTION
lI (GARBAGE,
TRASH, AND
BRUSH FEES)
OF APPENDIX
C (WYLIE COM-
PREHENSIVE FEE
SCHEDULE) OF
THE WYLIE CODE
OF ORDINANCES;
PROVIDING FOR
A PENALTY, Fo
THE VIOLATION
Oiiii-
ING FOR REPEAL-
ING, SAVINGS
AND SEVERABIL_
ITY CLAUSES;
PROVIDING FOR
AN EFFECTIVE
DATE OF THIS
ORDINANCE
AND PROVIDING
FOR THE PUBLI-
CATION OF THE
CAPTION HERE,
OF.
43- It- 342,334